4 Connecting Wired Dimming (Optional)
Dimming
Cable
Purple
Black/White (12V)*
Pink
Dimming
Switch
+ (0-10V)
- (0-10V)
3.4 Connection Schematic
Shorting cap
NOTE:
Arize Factor dimming allows user to adjust the light output from 0%/10-100%. When set to 0%, the system will enter standby
mode, consuming 0.5-1.5W and LEDs may remain very faintly lit. If 0 light is preferred, switch off the unit via the mains (AC line).
10
Installation Guide
Arize Factor
1
2
3
Driver Input Wire Colors
Brown = Line 1
Blue = Neutral or Line 2
Yellow/Green = Ground
AC line
Use proper circuit
protection level
Optional
inter-connection
cable
Driver
DC adapter
cable
AC input
cable
*Blue = Neutral or Line 2
*
*
*
Driver
Driver Driver Driver
N
3 Y
REPEAT FOR ENTIRE CIRCUIT BALANCING OUT EACH PHASE
3 ∆
L3
L2
L1
Driver
Driver
G
G
G
G
G
G
L
L
L
L
L
L
N
N
N
N
N
N
8
6
7
Lightbar
1
5
WARNING
Ambient temperature surrounding
each driver must be lower than 40°C.
WARNING
RISK OF ELECTRIC SHOCK
Turn power off before installation, inspection, cleaning or removal. And follow appropriate lock out/tag out safety procedure.
Remove cap from dimming
connector.
Plug dimming cable: align keying
features and push connectors
together until lock ring has snapped
into place and a click is heard. To
remove dimming cable, turn locking
ring 1/8 of a turn counter-clockwise
and separate connectors.
Connect the appropriate wiring to
Dim + (0-10V) and Dim – (0-10V)
from driver. Insulate the black wire.
Follow dimming switch instructions
for rest of connection.
*
The black/white wire is a 12V
auxiliary output that can support up
to 250mA of current.