AF-650 GP
Bussmann PN
Alternate External
Siba PN
Alternate External
Ferraz-Shawmut PN
[kW] / [HP]
Type JFHR2
Type JFHR2
90 / 125
170M3017
2061032,315
6.9URD30D08A0315
110 / 150
170M3018
2061032,35
6.9URD30D08A0350
132 / 200
170M4011
2061032,35
6.9URD30D08A0350
160 / 250
170M4012
2061032,4
6.9URD30D08A0400
200 / 300
170M4014
2061032,5
6.9URD30D08A0500
250 / 350
170M5011
2062032,55
6.9URD32D08A0550
315 / 400
170M4017
20 610 32.700
6.9URD31D08A0700
335 / 450
170M4017
20 610 32.700
6.9URD31D08A0700
355 / 500
170M6013
22 610 32.900
6.9URD33D08A0900
415 / 600
170M6013
22 610 32.900
6.9URD33D08A0900
500 / 650
170M7081
560 / 750
170M7081
710 / 950
170M7081
785 / 1050
170M7081
800 / 1150
170M7082
1000 / 1350
170M7083
Table 9.19 525–690V, above 125 HP
AF-650 GP
Bussmann PN
Rating
Alternate Siba PN
[kW] / [HP]
630 / 900
170M8611
1100A, 1000V
20 781 32.1000
710 / 1000
170M8611
1100A, 1000V
20 781 32.1000
800 / 1150
170M8611
1100A, 1000V
20 781 32.1000
900 / 1250
170M8611
1100A, 1000V
20 781 32.1000
1000 / 1350
170M8611
1100A, 1000V
20 781 32.1000
1200 / 1600
170M8611
1100A, 1000V
20 781 32.1000
Table 9.20 525–690V, 900 HP and above
*170M fuses from Bussmann shown use the -/80 visual indicator; -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and
amperage may be substituted for external use
**Any minimum 500V UL listed fuse with associated current rating may be used to meet UL requirements.
Installation
AF-650 GP Quick Guide
DET-759A
49
9
9