Legend for Generator Locations to reduce the risk of fire.
A
Standby weatherproof enclosure must be at least 5 ft
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
B
Exhaust outlet side of weatherproof enclosure must
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Typical Installations
NOTICE
The figures below show the minimum installation distances allowed to structures and items listed in legend.
C
Standby weatherproof enclosure must have a
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE
DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
A
A
A
A
A
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
Standby
Standby
Standby
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
Exhaust
Exhaust
Exhaust
A
A
5 ft (1.5 m) min.
5 ft (1.5 m) min.
Standby
5 ft (1.5 m) min.
Exhaust
B
B
B
B
NOT