8

ESL Wireless Smoke Detector

Specifications

Voltage................................................................................3VDC
Typical average standby current ................................. 35

µ

A

Typical test current........................................................... 2mA
Typical alarm current ..................................................... 70mA
Battery type ................................... Duracell

®

 3V lithium, 123

                                                    Panasonic

®

  lithium, CR123A

                                                           Sanyo

®

  lithium, CR123A

Low battery threshold........................................2.70V causes

                                       low battery signal

Sounder ................................... 85dBa at 10' temporal pattern
Low battery beep rate .......................1 every 45 sec. ± 2 sec.
Sensitivity ....................................................... 2.2% ± 1.3%/ft.
Operating temperature ..................40° to 100° F (4.4° to 37.8° C)
Operating humidity range .............. 0-95% non-condensing
RFI Immunity ........................... 20V/m minimum; 0-1000MHz

Color .................................................................................white
Alarm dimensions...................... 5.6" x 2.4" (14.2cm x 6.1cm)
Base dimensions ..........................5.4" x 0.96" (13.7cm x 1.17cm)
Drift compensation adjustment ....................... 0.5%/ft. max.
Heat detector specifications:

Rate-of-rise.............................................15° F/min > 105° F

                                 (8.3° C/min > 40.6° C)

Fixed .................................................................135° F ± 5° F

                                        (57.2° C ± 2.8° C)

RF frequency.....................................................902 - 928 MHz
Transmitter ID..................Pre-programmed, 1 Million codes
Modulation type................................................................AM
Signal format....................................................................PWM
Signal output types.............smoke alarm, heat alarm, tamper,

                             rate-of-rise alarm, test,  low battery,

                      trouble, supervisory

Listing ..................................................... UL268, CSFM, CE, FCC

For use with the following panels:

   ITI: Advent Commercial Fire 60-562-03 or 60-562-06, with software versions 1.62 and higher

Product Ordering

Patents: 4,855,713 & 4,864,636 & 5,686,885 & 5,686,896 & 6,396,405

Model

Description

60-992-900

ESL commercial wireless smoke detector, two 3V lithium batteries, 85dBa sounder,

thermal, base tamper, 319.5 MHz transmitter

Accessories

SM-200

Smoke! in a can

 

(canned smoke) for functional testing of smoke detectors

SMEXT-1

Extension tube for Smoke! in a can

211

Field replaceable optical chambers (set of 10)

60-933

6 pack 3V lithium batteries

www.GE-Interlogix.com

12345 SW Leveton Drive
Tualatin, OR 97062
Phone: 503-692-4052
USA & Canada: 800-547-2556
Technical Service: 800-648-7424
FaxBack: 800-483-2495

©  2004 GE Security
1039XXX-Rev. PRELIMINARY   09/04

2266 Second Street North
North St. Paul, MN 55109
www.GE-InterlogixSecurity.com
Phone: 651-777-2690
USA & Canada: 800-777-5484
Technical Service: 800-777-2624

GE Interlogix

 

Summary of Contents for 60-992-900

Page 1: ...dingly If the batteries are not replaced within seven days the detector s built in sounder emits a short beep or chirp every 45 seconds The detector also includes self diagnostics automatically adjusting its sensitivity accordingly to reduce the number of detector cleanings When cleaning becomes necessary the detector has a field replaceable optical chamber General Guidelines Before mounting detec...

Page 2: ...talled as follows 1 In all sleeping rooms 2 Outside of each separate sleeping area in the immediate vicinity of the sleeping rooms 3 On each level of the dwelling unit including basement NFPA 72 11 5 4 1Existing Apartment Buildings Detection Where required by applicable laws codes or standards for the specified for specified occupancy approved single and multiple station smoke alarms shall be inst...

Page 3: ...er levels of the building Smoke detectors may not warn in time when fires are caused by smoking in bed explosions improper storage of flammables overloaded electrical circuits or other hazardous conditions Programming This section describes the basic steps for programming learning the detector into panel memory For complete programming instructions refer to the specific panel installation instruct...

Page 4: ...fic panel installation instructions 4 After testing all detectors exit from Sensor Test mode Smoke Test The smoke test verifies that the detector activates when detecting smoke that the transmitted signal is received by the receiver panel and that the panel reports the alarm to the central monitoring station The smoke test should be performed annually 1 Contact the central monitoring station to al...

Page 5: ...d dispose of them properly 4 Observing correct polarity insert two new 3V lithium batteries into the battery compartment and replace the cover 5 Reattach the detector to the mounting base 6 Test the system Sensitivity Test Use this test to check detector sensitivity 1 Press and hold the detector test button for two seconds then release it The detector transmits a test signal then performs a self t...

Page 6: ...and maintenance When installed and used properly it requires minimal maintenance The smoke detector should be tested weekly See Testing the Detector Sensitivity and Smoke Testing the Detector When a detector requires maintenance it extinguishes its LED and sends a signal to the control panel as described in the following table 7 Line the new field replaceable optical chamber up with the optical ba...

Page 7: ...sed in the proper packing of detectors returned under this warranty as GE Interlogix will not be responsible for warranty repairs to equipment damaged because of improper packing The above warranty is in lieu of all other express warranties and implied warranties of merchantability and fitness for a particular purpose are limited in duration for a period of THREE years from the date of manufacture...

Page 8: ...ignal output types smokealarm heatalarm tamper rate of rise alarm test low battery trouble supervisory Listing UL268 CSFM CE FCC For use with the following panels ITI Advent Commercial Fire 60 562 03 or 60 562 06 with software versions 1 62 and higher Product Ordering Patents 4 855 713 4 864 636 5 686 885 5 686 896 6 396 405 Model Description 60 992 900 ESL commercial wireless smoke detector two 3...

Reviews: