background image

5

ESL Wireless Smoke Detector

Troubleshooting

The following describes how the detector indicates a fault condition. Correct fault conditions as soon as possible.

The LED stops working (no flashing or turning on) if the detector sensitivity is not within the normal range, or if an
unserviceable hardware fault is detected.

The detector stops transmitting supervisory signals if the detector has an unserviceable hardware fault or is not
sensitive enough, causing the panel to indicate the detector is in a supervisory condition. However, the detector can still
transmit alarm signals.

The detector transmits a trouble (CleanMe) signal when the detector is too sensitive. Panels supporting this feature
identify the trouble as “Partial Obscurity” on system touchpad displays.

When to Replace the Batteries

When the battery voltage gets low, the detector transmits a low battery signal for the panel to receive. The panel activates
trouble beeps through the system sirens and identifies the detector with the low battery on system touchpad displays. If the
batteries are not replaced within seven days, the detector’s built-in sounder emits a short beep or chirp every 45 seconds.
Detector chirps can be silenced for 24 hours by pressing the detector’s test button. Batteries should be replaced as soon as
possible (see “Specifications” for battery list).

Replacing the Batteries

Use only 3V lithium batteries listed in Specifications in the detector.

1. Remove the detector from the mounting base.

2. Slide the battery compartment cover away from the detector to unsnap it and lift it off. See Figure 3.

3. Remove the batteries and dispose of them properly.

4. Observing correct polarity, insert two new 3V lithium batteries into the battery compartment and replace the cover.

5. Reattach the detector to the mounting base.

6. Test the system.

Sensitivity Test

Use this test to check detector sensitivity.

1.

Press and hold the detector test button for two seconds, then release it. The detector transmits a test signal, then
performs a self-test that causes the LED to flash 1 to 9 times.

2.

Count the number of LED flashes, then use the following table to determine if any action is necessary.

Cleaning the Detector

Clean the detector cover with a dry or damp (water) cloth as needed to keep it free from dust and dirt.

When necessary, clean the detector interior and replace the optical chamber (part #211) as follows:

1. Notify the monitoring service that you will be performing maintenance to the system.

2. Remove the detector from its mounting base.

3. Remove the batteriesSee Replacing the Batteries.

4. Slide a flat-blade screwdriver in the slot on the detector cap and gently push the handle down to pry the detector cap up

and off. See Figure 5.

5. Squeeze the field replaceable optical chamber and pull it up and away from the optical base and discard. See Figure 6.

6. Blow out or use a soft-bristled brush to remove all dust and dirt from the optical base.

Flashes

Indication

Action

1

Unservicable hardware fault detected.

Reset unit by removing batteries and rerun sensitivity
test. If the error persists, replace the unit.

2-3

Detector is becoming insensitive.

Clean the unit. reset unit by removing batteries and rerun

sensitivity test. If the error persists, replace the unit.

4-7

Detector is within sensitivity range.

N/A

8-9

Detector is becoming too sensitive.

Verify that the smoke chamber is snapped down
securely. Clean the unit. Replace chamber part #211.

Summary of Contents for 60-992-900

Page 1: ...dingly If the batteries are not replaced within seven days the detector s built in sounder emits a short beep or chirp every 45 seconds The detector also includes self diagnostics automatically adjusting its sensitivity accordingly to reduce the number of detector cleanings When cleaning becomes necessary the detector has a field replaceable optical chamber General Guidelines Before mounting detec...

Page 2: ...talled as follows 1 In all sleeping rooms 2 Outside of each separate sleeping area in the immediate vicinity of the sleeping rooms 3 On each level of the dwelling unit including basement NFPA 72 11 5 4 1Existing Apartment Buildings Detection Where required by applicable laws codes or standards for the specified for specified occupancy approved single and multiple station smoke alarms shall be inst...

Page 3: ...er levels of the building Smoke detectors may not warn in time when fires are caused by smoking in bed explosions improper storage of flammables overloaded electrical circuits or other hazardous conditions Programming This section describes the basic steps for programming learning the detector into panel memory For complete programming instructions refer to the specific panel installation instruct...

Page 4: ...fic panel installation instructions 4 After testing all detectors exit from Sensor Test mode Smoke Test The smoke test verifies that the detector activates when detecting smoke that the transmitted signal is received by the receiver panel and that the panel reports the alarm to the central monitoring station The smoke test should be performed annually 1 Contact the central monitoring station to al...

Page 5: ...d dispose of them properly 4 Observing correct polarity insert two new 3V lithium batteries into the battery compartment and replace the cover 5 Reattach the detector to the mounting base 6 Test the system Sensitivity Test Use this test to check detector sensitivity 1 Press and hold the detector test button for two seconds then release it The detector transmits a test signal then performs a self t...

Page 6: ...and maintenance When installed and used properly it requires minimal maintenance The smoke detector should be tested weekly See Testing the Detector Sensitivity and Smoke Testing the Detector When a detector requires maintenance it extinguishes its LED and sends a signal to the control panel as described in the following table 7 Line the new field replaceable optical chamber up with the optical ba...

Page 7: ...sed in the proper packing of detectors returned under this warranty as GE Interlogix will not be responsible for warranty repairs to equipment damaged because of improper packing The above warranty is in lieu of all other express warranties and implied warranties of merchantability and fitness for a particular purpose are limited in duration for a period of THREE years from the date of manufacture...

Page 8: ...ignal output types smokealarm heatalarm tamper rate of rise alarm test low battery trouble supervisory Listing UL268 CSFM CE FCC For use with the following panels ITI Advent Commercial Fire 60 562 03 or 60 562 06 with software versions 1 62 and higher Product Ordering Patents 4 855 713 4 864 636 5 686 885 5 686 896 6 396 405 Model Description 60 992 900 ESL commercial wireless smoke detector two 3...

Reviews: