background image

4

ESL Wireless Smoke Detector

Mounting

Mount the detector with the appropriate fasteners. Mounting hardware is included (screws and anchors), however you may
need different hardware depending on the installation.

1.

Separate the detector from the mounting base by turning the detector counter clockwise about 15 degrees. The detector
should snap off of the mounting base.

2.

Place the mounting base on the mounting surface at the desired location and mark the mounting holes using a pencil.

3.

Secure the mounting base to the surface using the appropriate hardware.

4.

Attach the detector to the mounting base by lining up the alignment tab on the detector with the alignment arrow on the
mounting base, then put the detector on the base and turn it clockwise about 15 degrees. The detector should snap into
place.

Testing

There are three ways to test the detector: sensor test, smoke test, and sensitivity test.

Sensor Test

The sensor test verifies good communication between the detector and receiver/panel. The sensor test should be performed
weekly.

1.

Put the panel into Sensor Test mode (refer to the specific panel installation instructions).

2.

Press and hold the detector test button for 2 seconds. The detector transmits a test signal.

3.

Listen for the appropriate response from system sirens (refer to the specific panel installation instructions).

4.

After testing all detectors, exit from Sensor Test mode.

Smoke Test

The smoke test verifies that the detector activates when detecting smoke, that the transmitted signal is received by the
receiver/panel, and that the panel reports the alarm to the central monitoring station. The smoke test should be performed
annually.

1.

Contact the central monitoring station to alert them you are testing the system and they should not dispatch authorities.

2.

Activate the detector using one of the following two methods:

Method 1 Hold a smoldering punk or cotton wick close to the detector and direct the smoke into the smoke entry
openings for about 20 seconds.

Method 2 Use ESL Smoke! in a can

®

 and follow the directions on the can.

Once activated, the transmitter LED turns on, the built-in sounder emits a temporal 3 pattern, and the detector transmits
an alarm signal. The panel then processes the alarm signal and reports the alarm condition to the central station.

3.

Press the detector test button to stop the built-in sounder. The detector automatically resets when smoke is no longer
present and the LED should turn off and return to normal operation (one flash every 8 seconds).

4.

Contact the central monitoring to verify they received the alarm report.

5.

Be sure to alert the central monitoring station when you are finished testing.

Figure 5. Removing Detector Cap

Figure 3 - Battery Compartment

Figure 4 - Detector-to-Base Alignment

Battery compartment

Alignment tab

Alignment arrow

Summary of Contents for 60-992-900

Page 1: ...dingly If the batteries are not replaced within seven days the detector s built in sounder emits a short beep or chirp every 45 seconds The detector also includes self diagnostics automatically adjusting its sensitivity accordingly to reduce the number of detector cleanings When cleaning becomes necessary the detector has a field replaceable optical chamber General Guidelines Before mounting detec...

Page 2: ...talled as follows 1 In all sleeping rooms 2 Outside of each separate sleeping area in the immediate vicinity of the sleeping rooms 3 On each level of the dwelling unit including basement NFPA 72 11 5 4 1Existing Apartment Buildings Detection Where required by applicable laws codes or standards for the specified for specified occupancy approved single and multiple station smoke alarms shall be inst...

Page 3: ...er levels of the building Smoke detectors may not warn in time when fires are caused by smoking in bed explosions improper storage of flammables overloaded electrical circuits or other hazardous conditions Programming This section describes the basic steps for programming learning the detector into panel memory For complete programming instructions refer to the specific panel installation instruct...

Page 4: ...fic panel installation instructions 4 After testing all detectors exit from Sensor Test mode Smoke Test The smoke test verifies that the detector activates when detecting smoke that the transmitted signal is received by the receiver panel and that the panel reports the alarm to the central monitoring station The smoke test should be performed annually 1 Contact the central monitoring station to al...

Page 5: ...d dispose of them properly 4 Observing correct polarity insert two new 3V lithium batteries into the battery compartment and replace the cover 5 Reattach the detector to the mounting base 6 Test the system Sensitivity Test Use this test to check detector sensitivity 1 Press and hold the detector test button for two seconds then release it The detector transmits a test signal then performs a self t...

Page 6: ...and maintenance When installed and used properly it requires minimal maintenance The smoke detector should be tested weekly See Testing the Detector Sensitivity and Smoke Testing the Detector When a detector requires maintenance it extinguishes its LED and sends a signal to the control panel as described in the following table 7 Line the new field replaceable optical chamber up with the optical ba...

Page 7: ...sed in the proper packing of detectors returned under this warranty as GE Interlogix will not be responsible for warranty repairs to equipment damaged because of improper packing The above warranty is in lieu of all other express warranties and implied warranties of merchantability and fitness for a particular purpose are limited in duration for a period of THREE years from the date of manufacture...

Page 8: ...ignal output types smokealarm heatalarm tamper rate of rise alarm test low battery trouble supervisory Listing UL268 CSFM CE FCC For use with the following panels ITI Advent Commercial Fire 60 562 03 or 60 562 06 with software versions 1 62 and higher Product Ordering Patents 4 855 713 4 864 636 5 686 885 5 686 896 6 396 405 Model Description 60 992 900 ESL commercial wireless smoke detector two 3...

Reviews: