2-20
MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
FORMAT CODES
CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
20
T
21
U
22
V
23
W
24
X
25
Y
26
Z
F17
32 bits
UNSIGNED LONG VALUE, 3 DECIMAL PLACES
1st 16 bits
High Order Word of Long Value
2nd 16 bits
Low Order Word of Long Value
Example: 123456 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex
F18
32 bits
DATE MM/DD/YYYY
1st byte
Month 1 to 12
2nd byte
Day 1 to 31
3rd and 4th byte
Year 2000 to 2099
Example: Feb 20, 1995 stored as 34867142
i.e. 1st word: 0214, 2nd word 07CB
F19
32 bits
TIME HH:MM:SS:hh
1st byte
Hundredths of seconds 0 to 99
2nd byte
Seconds 0 to 59
3rd byte
Minutes 0 to 59
4th byte
Hours 0 to 23
Example: 2:05pm stored as 235208704
i.e. 1st word: 0E05, 2nd word 0000
F20
32 bits
2’s COMPLEMENT SIGNED LONG VALUE
1st 16 bits
High Order Word of Long Value
2nd 16 bits
Low Order Word of Long Value
Note: -1 means “Never”
F22
16 bits
TWO 8-BIT CHARACTERS PACKED INTO 16-BIT
UNSIGNED
MSB
First Character
LSB
Second Character
Example: String ‘AB’ stored as 4142 hex
FC101
16 bits
RS 485 Baud Rate
0
9600 baud
1
19200 baud
2
38400 baud
3
57600 baud
4
115200 baud
FC105
16 bits
CT Type
0
None
1
1 A Secondary
2
5 A Secondary
3
Direct Connect
FC107
16 bits
Supply Frequency
0
60
Code
Type
Definition