3-52
MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL
CHAPTER 3: FIELDBUS INTERFACE
17
Cool Time
Constant
Stopped
Mins
F1
1
1000
30
2
18
Hot/Cold Safe
Stall Ratio
Percent
F1
1
100
75
2
19
Standard
Overload Curve
None
F1
1
15
4
2
1A
Mechanical
Jam Level
FLA
F3B
101
451
451
2
1B
Mechanical
Jam Delay
Seconds F2
1
300
1
2
1C
Acceleration
Alarm Timer
Seconds F2B
5
2501
2501
2
1D
Acceleration
Trip Timer
Seconds F2B
5
2501
2501
2
1E
Current
Unbalance
Alarm Level
Percent
F1B
4
41
15
2
1F
Current
Unbalance
Alarm Delay
Seconds F1
1
60
1
2
20
Current
Unbalance Trip
Level
Percent
F1B
4
41
30
2
21
Current
Unbalance Trip
Delay
Seconds F1
1
60
1
2
22
CBCT Ground
Alarm Level
Amps
F2B
5
151
151
2
23
Ground Alarm
Delay On Start
Seconds F1
0
60
10
2
24
CBCT Ground
Trip Level
Amps
F2B
5
151
151
2
25
Ground Trip
Delay On Start
Seconds F2
0
100
0
2
26
Ground Alarm
Delay On Run
Seconds F1
0
60
10
2
27
Ground Trip
Delay On Run
Seconds F2
0
50
0
2
2D
Lockout Reset None
FC142
0
0xE000 0
2
2E
Access Switch None
FC142
0
0xE000 0
2
2F
Field
Permissive
None
FC142
0
0xE000 0
2
30
Comms
Permissive
None
FC142
0
0xE000 0
2
31
Forward Limit
None
FC142
0
0xE000 0
2
32
Reverse Limit
None
FC142
0
0xE000 0
2
33
Remote Reset None
FC142
0
0xE000 0
2
34
MCC
Permissive
None
FC142
0
0xE000 0
2
35
Hard Wired
Start A
None
FC142
0
0xE000 0
2
36
Hard Wired
Start B
None
FC142
0
0xE000 0
2
37
Hard Wired
Stop
None
FC142
0
0xE000 0
2
ATTRIBU
TE
DESCRIPTION UNIT
FORMAT
CODE
MIN
MAX
FACTORY
DEFAULT
SIZE IN
BYTES