background image

Notes 
**If the DALI cables are overloaded for a long period or short-circuited the DALI interface switches to “high impedance” until 
the fault is eliminated. The ON LED goes out and the fault LED lights up. The fault contact is not closed in this case. 
The DALI interface should be treated in the same way as mains voltage.

DALI interface on the controller

The DALI interface on the controller supplies the DALI interfaces of the connected DALI components. To ensure that the 
maximum summation current of 250 mA permitted for DALI is not exceeded no other DALI supplies or DALI controllers may 
be connected in this system. To ensure that the maximum permissible voltage drop on the interface cables of 2V in accor-
dance with the DALI specification is not exceeded the cable cross-section must be selected in accordance with the table in 
the technical data.

Notes:
1. Only appropriate DALI components may be connected to the DALI interface of the   controller. 
2. Exposure of the DALI interface of the controller to mains voltage may lead to damage or destruction of the controller. 
3. The controller must not be combined with a mains voltage operated 1-switch controller (=Touch Dim).

Mains failure/DALI failure

If the power supply to the controller fails the connected DALI units, which are still being supplied with power, are switched to 
maximum brightness (see also information supplied by the manufacturers). When power returns to the controller it automat-
ically restores the lighting system to its status prior to the failure. 

Replacing/expanding units

If DALI ECGs or DALI converters are added, make sure that the maximum number of 64 units is not exceeded. Newly added 
units should be incorporated in the system as described in “Group assignment”, already existing units should be confirmed 
with the master button. 
If units are removed, also the “Group assignment” has to pass and the existing units should be confirmed with the master 
button (see also “Group assignment”).

Control buttons

Normal commercially available buttons (make contacts with basic insulation) can be used. Between 1 and five buttons are 
needed depending on the application. The central button is needed for the construction site sum function; buttons T1 and T2 
are also needed for starting the system and for group assignment (they need to be close together as they have to be operat-
ed together).

If more than the first two groups and/or scenes are used, buttons T3 and T4 will be needed. Buttons may be connected in 
parallel to operate the lighting system from different places. Functions can be separated by installing buttons in different 
areas. The master button always acts on the entire system.

If all five buttons are to be provided at one location a rocker switch may be used for the master sum function, for example, 
and a 4-way rocker switch for T1 to T4.

Cable routes:

The relevant wiring requirements governing cable routes, insulation, fusing and 
minimum cross-sections must be observed.

Design:

Insulation casing Snap-on mounting for rails, for surface mounting and installa-
tion in distributor

Dimensions:

WxHxD=140x90x61mm (8TE)

Weight:

approx. 550g

Labelling:

CE

Terminal assignment:

see wiring diagrams and information printed on unit
If incorrectly connected there is a risk of failure, malfunction or destruction

Summary of Contents for DALI 64668

Page 1: ...GE Lighting Operating instructions DALI Indoor Lighting Control Solution Type DALI Type 1 SKU 64668 ...

Page 2: ...ht motion sensors 7 Safety and installation instructions 7 Technical data 8 9 DALI interface on the controller 9 Mains failure DALI failure 9 Replacing expanding units 9 Control buttons 9 Wiring diagrams with brief descriptions 10 13 DALI Controller without sensors lighting control 10 DALI Controller with a light sensor at LS1 Group 1 lighting control 11 DALI Controller with two light and motion s...

Page 3: ...by means of the wiring When someone enters the room the presence function activates scene 1 constant light scene If a different setting is select ed for example scene 2 for a presentation this setting will remain in force until the system reverts to its basic state a certain time after the last person has left the room The sensors start working as soon as power is supplied to the Type 1 Controller...

Page 4: ...ault LED goes out Note A reset will cancel all group assignments and scene settings Group assignment Group assignments are locked by a code so they cannot be inadvertently changed The procedure for removing this lock is as follows Hold down the master button T1 and T2 simultaneously for about 5 seconds until the entire system flashes Now release the buttons In the next 10 seconds press the master ...

Page 5: ...ton when they are identified by the controller the lamp s in the unit will flash For units that are to be reassigned the new group is selected by pressing the relevant switch T1 to T4 The assignment is stored by pressing the master button Notes 1 Changes to the group assignments are not reflected in existing lighting scenes For this reason the lighting scenes have to be reset and stored after the ...

Page 6: ...system flashes once by way of confirmation The lighting mood you set up is now stored as scene 2 Calling up scenes Scenes 1 to 4 are called up by pressing T1 to T4 It takes about three seconds to switch from one scene to another cross fading the change is a fluent one If light sensors are connected to the controller groups 1 to 3 are controlled The time required to cross fade to scene 1 de pends o...

Page 7: ...light motion sensors The light motion sensors specified in the Accessories section can be connected from one to six light or light motion sen sors depending on the application There is one input available for motion detection three double terminals All the motion sensors connected here operate in parallel extending the detection area Depending on the application the light sensors may all be connec...

Page 8: ...6V 150mA DC DA IK 250mA DC max 22 5V DC electr Current limiter overtemperature protection Switch inputs 5 switch inputs 5V DC make contacts T1 to T4 Master T5 Sensor inputs 3 x light sensors analog 0 4VDC 1x motion 5V DC LS1 to LS3 B Light value range see technical specification for the light sensors Sensor supply approx 10V 15mA DC supply for sensors Vcc DALI interface switch inputs and sensor te...

Page 9: ...ding units If DALI ECGs or DALI converters are added make sure that the maximum number of 64 units is not exceeded Newly added units should be incorporated in the system as described in Group assignment already existing units should be confirmed with the master button If units are removed also the Group assignment has to pass and the existing units should be confirmed with the master button see al...

Page 10: ...used make contacts The switches can be connected in parallel so the system can be controlled from different locations An optional signal lamp may be connected Other connections are possible thanks to the floating contact make sure to comply with technical data L PE N Mains 230V ac 50 60Hz Signal lamp optional 230V ac error L N 19 27 17 25 20 28 6 5 7 M 13 15 LS3 LS2 LS1 12 11 4 3 0V sensors 16 8 V...

Page 11: ...s and Lighting scene 1 A maximum of 64 DALI units can be switched and dimmed The DALI units can be assigned to as many as four groups Up to four lighting scenes can be stored and called up Standard switches are used make contacts The switches can be connected in parallel so the system can be controlled from different locations An optional signal lamp may be connected Other connections are possible...

Page 12: ...ne is in the room the entire lighting system is switched off after an adjustable delay When someone enters the room again lighting scene 1 is activated See also Sensors and Lighting scene 1 A maximum of 64 DALI units can be switched and dimmed The DALI units can be assigned to as many as four groups Up to four lighting scenes can be stored and called up Standard switches are used make contacts The...

Page 13: ... no one is in the room the entire lighting system is switched off after an adjustable delay When someone enters the room again lighting scene 1 is activated See also Sensors and Lighting scene 1 A maximum of 64 DALI units can be switched and dimmed The DALI units can be assigned to as many as four groups Up to four lighting scenes can be stored and called up Standard switches are used make contact...

Page 14: ...t button the mode can now be set to the desired setting By a long holding down approx 10 seconds of the reset button the chosen adjustment is stored LED signals in common the storage by a singly flash and mode is left to the normal operation Visualisation of the locking mode Controller is in operation operation LED green is flashing If in the locking mode an arbitrary control button is pressed the...

Page 15: ...and set up Area designation Unit ref number Sensor ref number Group 1 at LS 1 Group 2 at LS 2 Group 3 at LS 3 Group 4 none open loop control group Area designation number Master button s Scenes designation Switch es T1 Switch es T2 Switch es T3 Switch es T4 ...

Page 16: ...3 sets of strip lighting Presence detection delay can be adjusted between 1 and 32 minutes Controller and power supply for the DALI interfaces integrated in one unit No separate DALI supply required Feedback messages from the DALI system via a relay contact and LEDs on the unit System messages e g DALI lamp faults DALI faults etc Support for checking the system installation construction site mode ...

Page 17: ...ciju i informacija o bezbednosti na srpskom jeziku možete pronaći na sledećoj lokaciji Slovenska različica navodil za namestitev in varnostnih navodil se nahaja na naslednji strani A telepítési útmutató és a biztonsági információk magyar nyelvű változata az alábbi címen található De Nederlandse versie van de installatie instructies en veiligheidsinformatie kan op de volgende locatie worden gevonde...

Reviews: