DALI Controller with three light and motion sensors at LS1 to LS3
Lighting scene 1: Lighting control of group 1, group 2 and group 3 (e.g. 3 sets of strip lighting)
Presence detection with extension of detection area
• The combined sensors are connected with the light outputs at terminals LS1 to LS3 and therefore
assigned to groups 1 to 3.
• Lighting control of groups 1 to 3 takes place in lighting scene 1 (e.g. 3 sets of strip lighting).
• Group 4 remains an open-loop control group even in lighting scene 1.
• If there is enough daylight available the relevant group is dimmed to its minimum value and switches
off after 10 minutes.
• The motion outputs are connected in parallel, which provides more sensitive detection in a small area
or enables the detection area to be enlarged to cover large rooms.
• If no one is in the room the entire lighting system is switched off after an adjustable delay.
• When someone enters the room again lighting scene 1 is activated.
See also Sensors and Lighting scene 1.
• A maximum of 64 DALI units can be switched and dimmed.
• The DALI units can be assigned to as many as four groups.
• Up to four lighting scenes can be stored and called up.
• Standard switches are used (make contacts).
• The switches can be connected in parallel so the system can be controlled from different locations.
• An optional signal lamp may be connected. Other connections are possible thanks to the floating con-
tact (make sure to comply with technical data).
F2
L
PE
N
Mains 230V ac
50/60Hz
Signal lamp
(optional)
230V ac
error
L
N
19 27
17
25
20 28
6
5
7
M
13
15
LS3
LS2
LS1
12
11
4
3
0V
sensors
16
8
Vcc
DA+
9
2
10
1
DA-
24
23
22
T4
32
31
30
21
29
0V
T1
Master
Controls
14
T2 T3
F1
6A
max
To the DALI units
(ECGs, converters, etc.)
L
N
PE
DA
DA
-
+
LS 0V Vcc
-
+
LS 0V Vcc
-
+
LS 0V Vcc
M
DALI CB Type 1
MS-C
MS-C
M
MS-C
M