Type:
DALI Type 1
SKU:
64668
Power input:
approx. 4W - 9W depending on load
Fuse protection:
unit/fault contact external 6A
Operating temperature:
0°C to 45°C
Protection class:
II (total insulation)
Type of protection:
IP20
Pollution severity:
2 (dry not conductive)
Fault contact (µ):
- Floating rely contact (make contact) max. 250Vac/5Aac µ contact gap: function
switching, no reliable isolation
- Reports lamp fault. For lamp fault contact closed and fault LED on.
- Reports DALI fault (interruption/short-circuit/no DALI units), Cycle fault LED and relay contact.
**Display LEDs on the unit:
ON green lights if the unit is operational
Send yellow lights when data is being sent via the DALI interface
Fault red lights if there is a lamp fault for a DALI ECG (relay contact closed). flashes if there is
a DALI fault (on/off in synchronism with relay lights when reset button is pressed with power
on for as long as this button needs to be pressed to activate the reset (approx. 10 s).
Reset button:
- If the reset button is held down for approx. 10 s with power on the entire system is
placed in a defined initial state (groups deleted, scenes predefined).
- a short press during operation activates button test mode.
Overshoot time:
Motion timeout, can be set between 1 and 32 minutes with trimmer on unit.
DALI interface:
Interface complying with the DALI specification, polarized interface
Power supply for DALI units - approx. +16V/150mA DC (DA+)
- IK<250mA DC, max. 22.5V DC
- electr. Current limiter, overtemperature protection
Switch inputs:
5 switch inputs (<5V DC) (make contacts) T1 to T4, Master (T5)
Sensor inputs:
3 x light sensors (analog 0-4VDC), 1x motion (<5V DC) LS1 to LS3, B
Light value range:
see technical specification for the light sensors
Sensor supply:
approx. +10V/15mA DC (supply for sensors) Vcc
DALI interface, switch inputs and sensor terminals have basic insulation, no safety extra-low voltage.
Terminals:
Screw terminals: - solid 2 x 0.3 - 2.5 mm2
- stranded wire with sleeve 2 x 0.3 - 1.5 mm2
Mains:
L, N
Term. no. (19/27, 20/28) 19 and 27, 20 and 28 connected internally
Fault:
Fault contact Term. no. (17, 25)
DALI interface:
DA+ DA- Term. no. (1/9, 2/10) 1 and 9, 2 and 10 connected internally
Term. no. 1 and 9 (DALI supply DA+), 2 and 10 (DA- (0V))
Light sensor inputs:
LS1, LS2, LS3
Term. no. (13, 14, 15)
Motion input:
PD Term. no. (5/6/7)
5 and 6 and 7 connected internally
Sensor supply:
Vcc
Term. no. (8/16) 8 and 16 connected internally
0V sensors:
0V Terminal no. (3/4/11/12) 3 and 4 and 11 and 12 connected internally
Switch inputs:
T1 to T4, Master (T5)
Term. no. (21, 22, 23, 24, 29)
0V switch:
0V Term. no. (30/31/32) 30 and 31 and 32 connected internally
not used:
NC, NC Terminal no. (18, 26)
must not be used
Maximum cable lengths:
100m
- for DALI cables
300 m at 1.5 mm2
(Distance between the two DALI ECGs furthest apart)
Cable cross-section in mm2
2x0.5
2x0.75
2x1.0
2x1.5
Cable length (distance)
100
150
200
300
The DALI and mains cables may be laid together in one cable (e.g. 5x1.5 NYM) with appropriate insulation.
The sensor and switch cables must be laid separately.
Technical data