DALI Controller with a light sensor at LS1
Lighting scene 1: Group 1 lighting control
• The light sensor is connected at light sensor input LS1 and therefore assigned to group 1.
• Group 1 lighting control takes place in lighting scene 1.
• Groups 2 to 4 remain open-loop control groups even in lighting scene 1 because there are no light
sensors connected.
• Further light sensors can be connected in parallel to the light sensor at LS1 to produce an average
value.
• If there is enough daylight available group 1 is dimmed to its minimum value and switches off after 10
minutes.
See also Sensors and Lighting scene 1.
• A maximum of 64 DALI units can be switched and dimmed.
• The DALI units can be assigned to as many as four groups.
• Up to four lighting scenes can be stored and called up.
• Standard switches are used (make contacts).
• The switches can be connected in parallel so the system can be controlled from different locations.
• An optional signal lamp may be connected. Other connections are possible thanks to the floating con-
tact (make sure to comply with technical data).