NX-8 Commercial Fire
9
TERM
DESCRIPTION
LOC
PG
Log Full Report
A report can be sent to the central station when the event log is full.
37
21
Lost Clock
Service Light
The NX-8-CF can be programmed to display the "Service Required"
message when the internal clock has an invalid time due to power loss.
37
21
Manual Test
The NX-8-CF can be programmed to perform a bell and/or communicator
test when
is entered while the system is in the disarmed state.
37
21
On Board Zone
Disable
The eight zones on the NX-8-CF panel can be disabled in order to have a
completely wireless alarm system.
37
21
Partitions
The NX-8-CF can be partitioned into a maximum of eight separate
systems with distinct reporting codes, user codes, and operating features
for each system.
26-36
20-21
Program Code
Factory default:
when using a 4-digit code and
if the 6-digit option is used
.
The program code can
also be used as an Arm/Disarm code. If used as an Arm/Disarm code,
and open/close reports are sent, the user code will be 255.
43
23
Quick Arm
The NX-8-CF has a one-button "Quick Arm" feature, which can be used
to arm the system by pressing EXIT or STAY on the keypad. If closing
reports are sent, the user code will be 98.
23
18
Recent Closing
If enabled, the NX-8-CF will send a "Recent Closing Report" to the
central station if an alarm occurs within 5 minutes after the panel is
armed. The user number that armed the system will also be sent.
23
18
Re-exit
The NX-8-CF has the ability to restart the exit delay for a quick exit
without disarming the system by pressing EXIT while the system is
armed.
23
18
Relays
The NX-8-CF has two separate normally open and normally closed relay
contacts for a variety of applications, including access control, home
control/automation, wireless interfaces, and security functions.
Access control and home automation have not been verified by
UL testing.
45-48,
TERMINAL
DESCRIPTION
24
48
Siren Blast For
Arming
The NX-8-CF can be programmed to give a one second siren blast when
the panel is armed, at the end of the exit delay, or when the central
station receiver acknowledges the closing report. It can also give one
blast for remote (keyswitch) arming and two blasts for remote disarming.
37
21
Siren Supervision
The NX-8-CF has a
A
Siren Supervision
@
circuit that will constantly monitor
the siren on the NX-8-CF and can be programmed to report if the wires
are cut.
37
21
Silent Exit Option
The exit delay can be silenced by pressing
r
EXIT before arming the
control panel or when using the re-exit feature. The exit delay can also
be silenced permanently in all partitions.
37
21
Start / End
Programming
A report can be sent when local programming is started and ended.
37
21
Technical Manuals Online! - http://www.tech-man.com