LOC
PG
DESCRIPTION
DEFAULT
DATA
Segment #5
1 = Lost Clock “Service Required” message enable
‘
2 = Reserved
3 = Disable on-board eight zones
‘
4 = Enables two trips on the same cross-zone to activate the alarm
‘
5 = Disables bypass reports for force armed zones
‘
6 = Silent exit
‘
7 = Clock uses internal crystal
‘
8 = Disable Temporal Siren on Fire (Do not disable on UL listed systems)
‘
38
22
SWINGER SHUTDOWN COUNT
0
_
KEYPAD SOUNDER CONTROL
Segment #1
39
22
1 = Keypad sounds for Telephone Line Cut when in the Armed state
‘
2 = Keypad sounds for Telephone Line Cut when in the Disarmed state
‘
3 = Keypad sounds upon AC Power Failure
‘
4 = Keypad sounds upon Low Battery Detection
‘
5 = Keypad sounds during
Cross Zone
Trip Time
‘
6 = Keypad sounds for Tamper Alarm
‘
7 = Reserved
8 = Keypad sounds for expander trouble (required for UL)
‘
SYSTEM TIMERS
Segment #1 Dynamic Battery Test duration (0-255
minutes)
0
_____
Segment #2 AC Failure report delay (0-255 hours)
6
_____
Segment #3 Power Up Delay (0-60 seconds)
0
_____
Segment #4 Siren Time (1-255 minutes)
8
_____
Segment #5 Telephone Line Cut delay (10-175 seconds)
30
_____
Segment #6
Cross Zone
Time (0-255 minutes)
5
_____
Segment #7 Chime Time in 50 mS increments (0-255)
3
_____
Segment #8 Dialer delay ( 0-255 seconds)
0
_____
Segment #9 Fire Alarm Verification Time (120-240 sec.)
0
_____
40
22
Segment #10 Reserved
SPECIAL FEATURES
Segment #1
41
23
1 - 2 = Reserved
3 = Enable
Auto Cancel / Abort
‘
4 = Enable
Walk-Test Mode
‘
5 - 8 = Reserved
42
23
GO TO PROGRAM CODE
9-7-1-3-0-0
_ _ _ _ _ _
GO TO PROGRAM CODE PARTITION AND AUTHORIZATION
Segment #1
1 = Reserved
2 = Enables "Go To Program Code" as an arm only code
‘
3 = Enables "Go To Program Code" as an arm only after closing
‘
4 = Enables "Go To Program Code" as a master arm/disarm code (can change user codes)
‘
5 = Enables "Go To Program Code" as an arm/disarm code
‘
6 = Enables "Go To Program Code" to bypass zones
‘
7 = Enables "Go To Program Code" opening and closing reports
‘
8 = Reserved
Segment #2
43
23
1 = Enables "Go To Program Code" for partition #1
‘
2 = Enables "Go To Program Code" for partition #2
‘
3 = Enables "Go To Program Code" for partition #3
‘
4 = Enables "Go To Program Code" for partition #4
‘
5 = Enables "Go To Program Code" for partition #5
‘
6 = Enables "Go To Program Code" for partition #6
‘
7 = Enables "Go To Program Code" for partition #7
‘
8 = Enables "Go To Program Code" for partition #8
‘
44
24
DURESS CODE
15-15-15-15-15-15
___ ___ ___ ___ ___ ___