NX-8 Commercial Fire
22
Segment 2
1 = On if siren driver should be a voltage output. Off if on board siren driver enabled.
2 = On if siren sounds for expander trouble (required for UL installations).
3 = On for Immediate Restore by zone. Off for zones to restore only when siren is off.
4 = On if Dynamic Battery Test performed at arming. Off if performed at disarming. (Loc. 40)
5 = On if Battery Missing Test is performed every 12 seconds.
6 = On if Manual Bell Test performed during [
r
]-[4] test function.
7 = On if Manual Communicator Test performed during [
r
]- [4] test function.
8 = On if Box Tamper terminals on the control panel are enabled.
Segment 3
1 = On if
Box Tamper
report enabled.
2 = On if
AC Fail
reporting enabled.
3 = On if Low Battery reporting enabled.
4 = On if Aux. Power Overcurrent report enabled.
5 = On if Siren Supervision report enabled.
6 = On if Telephone Line Cut report enabled.
7 = On if Ground Fault Detection report enabled.
8 = On if Expander Trouble reporting enabled.
Segment 4
1 = On if Fail To Communicate report enabled.
2 = On if Log Full report enabled.
3 = On if Autotest report enabled.
4 = On if Start/End programming report enabled.
5 = Reserved.
6 = On if Sensor Low Battery report enabled.
7 = On if Sensor Missing report enabled.
8 = Reserved.
Segment 5
1 = On enables Lost Clock “Service Required” message.
2 = Reserved
3 = On disables On-Board 8 zones.
4 = On will allow two trips on same cross-zone to activate an alarm.
5 = On will not allow zones that are force armed to report bypass.
6 = On enables Silent Exit option.
7 = Use internal crystal for clock.
8 = Disable Temporal Siren on Fire. NOTE: DO NOT disable for UL listed systems.
LOCATION 38 -
SWINGER SHUTDOWN
COUNT
Location 38 contains the number of trips during an arming cycle that the NX-8-CF will allow before bypassing a zone.
The count determination is described in the GLOSSARY on page 6. NOTE: For UL installations, this feature shall
be disabled.
LOCATION 39 -
KEYPAD SOUNDER CONTROL
(1 segment, feature selection data)
Segment 1
1 = On if keypad sounds for
A
Telephone Line Cut
@
when the system is armed.
2 = On if keypad sounds for
A
Telephone Line Cut
@
when disarmed.
3 = On if keypad sounds upon AC Power Failure.
4 = On if keypad sounds when a Low Battery is detected.
5 = On if keypad sounds during
Cross Zone
trip time.
6 = On if keypad sounds for zone and
box tamper
s.
7 = Reserved.
8 = On if keypad sounds for expander trouble (required for UL installations).
LOCATION 40 - SYSTEM TIMERS
(10 segments, numerical data) Location 40 contains the duration of various system timing functions. Example: If you
desire the duration of the Dynamic Battery Test to be 30 minutes, program [3]-[0]-[
r
] in segment 1 of this location. The
[3]-[0] is the number of minutes, and the [
r
] stores the data and moves to the next segment of this location.