NX-8 Commercial Fire
18
Segment 1
1=
Partition #1
5=
Partition #5
2=
Partition #2
6=
Partition #6
3=
Partition #3
7=
Partition #7
4=
Partition #4
8=
Partition #8
LOCATIONS 18 – 22 RESERVED
LOCATION 23 - PARTITION 1, FEATURE AND REPORT SELECTIONS
(3 segments, feature selection data) Location 23 is used to enable certain features that can be accessed or are visible
to the user from the keypad of the system. In addition, certain communicator reports are enabled in location 23. Each
of these features can be enabled by partition. For additional partition information see locations 88-109. If the feature
selection location for any partition is left blank, that partition will use this location for the feature selection.
This location contains 3 segments of 8 features each. (Refer to GLOSSARY on page 6.)
Segment 1
1 = On enables the
Quick Arm
feature.
2 = On enables the Re-exit feature.
3 = On enables the
Automatic Bypass
feature.
4 = On enables the Silent Keypad Panic feature (overrides the audible panic selection).
5 = On enables the
Audible Keypad Panic
feature.
6 = On enables the Keypad Aux 1 feature (FIRE).
7 = On enables the Keypad Aux 2 feature (AUXILIARY).
8 = On enables the Keypad Multiple Code Attempt Tamper feature.
Segment 2
1 = On enables the LED Extinguish feature.
2 = On enables the Require Code for Bypassing feature.
3 = On enables the Zone Bypassed Sounder Alert feature.
4 = Reserved
5 = On enables Bypass toggle.
6 = On enables Silent Auto Arm.
7 = On enables the Automatic Instant feature.
8 = Reserved.
Segment 3
1 = On enables Opening and Closing reports.
2 = On enables Zone Bypass reporting.
3 = On enables Zone Restore reporting. Factory default is on.
4 = On enables Zone Trouble reporting. Factory default is on.
5 = On enables Zone Tamper reporting.
6 = On enables the Cancel reporting.
7 = On enables the
Recent Closing
report.
8 = On enables the Exit Error report.
LOCATION 24 - ENTRY / EXIT TIMERS
(4 segments, numerical data) Location 24 is used to program the Entry/Exit times. There are 2 separate Entry/Exit
times.
Segment 1,
Entry time 1:
This is the entry time that will be used when a delay 1 zone type initiates an entry
delay. Valid entries are 10-255 seconds.
Segment 2,
Exit time 1:
This is the exit time that will be used for all zones designated as delay 1. Valid entries
are 10-255 seconds.
Segment 3,
Entry time 2:
This is the entry time that will be used when a delay 2 zone type initiates an entry
delay. Valid entries are 10-255 seconds.
Segment 4,
Exit time 2:
This is the exit time that will be used for all zones designated as delay 2. Valid entries
are 10-255 seconds.