55
C-6000-ESP PLC STATUS LIGHTS
54
C-6000-ESP PLC STATUS LIGHTS
X
(Inputs)
DESCRIPTION OF PLC STATUS LIGHTS
GENERAL
DESCRIPTION
0
On
while “Fire Test Switch” is pushed and held, or hood is in Internal
Fire Mode.
Off
during "Cool Down Cycle".
Internal Fire Mode
1
On
when Break Glass Pull Station is activated, or when hood is in
External Fire Mode.
External Fire Mode
(Remote Fire Switch)
2
On
normally. It shuts
off
if cabinet is equipped with Low Detergent
alert feature and the detergent is low.
Low Detergent (Local)
3
Off
normally.
On
when Jumper is installed to disable Wash
Solenoids from opening during Internal Fire Mode and External Fire
Modes.
Disable Wash Solenoids during an
Internal or External Fire
4
Off
normally.
On
when Jumper is installed to enable Wash
Permission Signal.
Wash Permission Signal
5
On
when signal from External Control is sent to Start Fan
Start Fan (External)
6
On
when signal from External Control is sent to Start Wash
Start Wash (External)
7
On
normally. It shuts
off
if cabinet is equipped with Low Detergent
alert feature and the detergent is low.
Low Detergent (Remote)
8
On
when signal from External Control is sent to Start Fan
Start Fan/Start Wash (External)
9
Not Used
A
Not Used
B
Not Used
C
Not Used
D
Not Used
E
Not Used
F
Not Used
Y
(Outputs)
DESCRIPTION OF PLC STATUS LIGHTS
GENERAL
DESCRIPTION
0
On
when Wash Solenoid # 1 should be open.
Wash Solenoid #1
1
On
during an Internal or External Fire Mode. On during "Cool Down
Cycle".
Alarm / Fire Mode
2
On
when Detergent Pump (Local) should be on.
Detergent Pump (Local)
3
On
when Exhaust Fan should be on.
Exhaust Fan
4
On
when Supply Fan should be on.
Supply Fan
5
On
when damper is in "Wash" position, or while damper is
moving to "Wash" position
Damper Drive Signal to Wash
Position
6
On
when Detergent Pump (Remote) should be on.
Detergent Pump (Remote)
7
Not Used
COM
Never comes on
Y
(Outputs)
DESCRIPTION OF STATUS LIGHTS
GENERAL
DESCRIPTION
0
On when Wash Solenoid # 2 should be open.
Wash Solenoid #2
1
On when Wash Solenoid # 3 should be open.
Wash Solenoid #3
2
On when Wash Solenoid # 4 should be open.
Wash Solenoid #4
3
On when Wash Solenoid # 5 should be open.
Wash Solenoid #5
4
On when Wash Solenoid # 6 should be open.
Wash Solenoid #6
5
On when Wash Solenoid # 7 should be open.
Wash Solenoid #7
6
On when Wash Solenoid # 8 should be open.
Wash Solenoid #8
7
On when Wash Solenoid # 9 should be open.
Wash Solenoid #9
COM
Never comes on
(SEQUENTIAL WASH "S10-S13") DESCRIPTION - EXPANSION MODULE #2
Y
(Outputs)
DESCRIPTION OF STATUS LIGHTS
GENERAL
DESCRIPTION
0
On when Wash Solenoid # 10 should be open.
Wash Solenoid #10
1
On when Wash Solenoid # 11 should be open.
Wash Solenoid #11
2
On when Wash Solenoid # 12 should be open.
Wash Solenoid #12
3
On when Wash Solenoid # 13 should be open.
Wash Solenoid #13
4
Not Used
5
Not Used
6
Not Used
7
Not Used
STANDARD (SINGLE OR SEQUENTIAL WASH) DESCRIPTION - PLC
(SEQUENTIAL WASH "S2-S9") DESCRIPTION - EXPANSION MODULE #1
Summary of Contents for ClearAir RSPC-ESP SERIES
Page 9: ...9 TYPICAL INSTALLATION ...
Page 46: ...46 PARTS DETERGENT PUMP 45 PARTS DETERGENT PUMP ...
Page 53: ...53 C 6000 ESP INTERNAL WIRING DIAGRAM ...
Page 56: ...56 RSPC ESP DRAIN ...
Page 57: ...57 SPRAY ODOR WIRING ...
Page 68: ...INTENTIONALLY LEFT BLANK ...