Pulse-out I/F Board (M06587A001) Jumper Settings

Page 8

MDE-4864B Gasboy® 9820 Pump Interface Kits Installation Instructions · March 2022 

Pulse-out I/F Board (M06587A001) Jumper Settings

Jumpers JP1, JP2, and JP3

This board assembly can be configured for use in one of the following pump/dispenser 
configurations:

• Dual-channel, Single-hose Pulse-out I/F (see 

Figure 5 

on 

page 9

).

• Single-channel, Dual/Single-hose Pulse-out I/F (Refer to 

MDE-4567 9120K & 9820K 

Series AST Pumps Installation and Operation Manual

 for the wiring diagram, for models 

equipped with the old CPU. For models with the new CPU, refer to 

MDE-4652 Atlas 9800 

Electronics Field Installation Instructions

).

The table below shows the jumper settings and terminal block positions to connect at the 
bottom of the register, based on the configurations.

Check JP1 - JP3 jumpers and change them, if necessary. The jumper settings must be changed 
only when power to the pump/dispenser is removed, to protect the circuit that they are 
connected to.

In the model 9820 Pump, the P3 Connector is not connected.

Jumper Settings

Single-channel, Dual/Single-hose 

Pulse-out I/F (Default Setting)

Dual-channel, Single-hose Pulse-out I/F

Terminal Block 
Position

JP1 Position 1
JP2 Position 1
JP3 Open

JP1 Position 2
JP2 Position 2
JP3 Open

TB3-1

Pulse-out

Pulse-out A

TB3-2

No Connection

Pulse-out B

TB3-3

Return

Return A

TB3-4

No Connection

Return B

Summary of Contents for 9820

Page 1: ...llation of the kit Flat tip Screwdriver Cross tip Screwdriver Standard Socket set Parts List The following table lists the parts included in the Pump Interface Kits Sr No Description Part Number Quant...

Page 2: ...n and Operation Manual Gasboy Atlas Pumps Dispensers MDE 4652 Atlas 9800 Electronics Field Installation Instructions Gasboy Atlas Pumps Dispensers Abbreviations and Acronyms Term Description DEF Diese...

Page 3: ...lations must be followed Failure to install inspect maintain or service this equipment in accordance with these codes regulations and standards may lead to legal citations with penalties or affect the...

Page 4: ...n IMPORTANT Oxygen may be needed at scene if gasoline has been ingested or inhaled Seek medical advice immediately Lockout Tagout Lockout Tagout covers servicing and maintenance of machines and equipm...

Page 5: ...m Refer to MDE 4567 9120K 9820K Series AST Pumps Installation and Operation Manual and your Fuel Management System Installation Manual before proceeding To install the Gasboy 9820 Pump Interface Kit p...

Page 6: ...Assembly Loosen the Screws Tag the Wires 4 Note down the wiring or tag all the wires that are connected to the terminal blocks Remove all the wires from the terminal blocks 5 If the model 9820 Pump co...

Page 7: ...ed wire in position 1 Secure the terminal block using the 8 32 hardware Figure 4 Installing the Terminal Block Chassis Cable 8 32 Hardware 9 Carefully route the cable and install the connector on P1 o...

Page 8: ...fer to MDE 4652 Atlas 9800 Electronics Field Installation Instructions The table below shows the jumper settings and terminal block positions to connect at the bottom of the register based on the conf...

Page 9: ...puts from a single pulser Figure 5 Dual channel Single hose Pulse out I F REMOTE REGISTER Notes 1 All wiring and conduit runs must conform with all building fire codes all Federal State and Local code...

Page 10: ...and are for identification purposes only Use of these names logos and brands does not imply endorsement 2022 GASBOY 7300 West Friendly Avenue Post Office Box 22087 Greensboro North Carolina 27420 Phon...

Reviews: