36
4.3 Detector Calibration
Gas Alarm Systems recommends that you check
detectors routinely to ensure correct calibration and
operation.
Gas detectors require recalibration at least every 3 to 6
months. Fire detectors should be tested with the same
frequency. Site procedures may require more frequent
testing. See section 2.12 on page 14 for calibration
instructions.
For detailed instructions on the routine functional
testing of detectors, please refer to the relevant
Installation, Operating and Maintenance Instructions
provided with each detector.
4.4 Changing Batteries
During routine servicing, it is recommended that the
power be isolated from Gasmaster temporarily to
ensure that the back-up batteries are operational. Gas
Alarm Systems recommend that batteries are changed
every two years, and replaced as a pair.
Replacement batteries should be Yuasa UCEL Y1.2-12,
12 v 1.2 Ah C20 lead-acid type cells.
A 10 A fuse is fitted to the batteries, for replacement
part number see Spare Parts and Accessories section.
Batteries should be checked regularly on units
operating over 40ºC.
Warning
When replacing batteries, care should be taken to
ensure cables are re-fitted as shown on the battery
connection diagram. Incorrect fitment of battery
cables may result in a fire and/or harm to personnel.
4.5 Module Replacement
In the unlikely event of a Gasmaster component failure,
Gas Alarm Systems recommend that repair should
not be undertaken by anyone other than Gas Alarm
Systems approved personnel. Please contact Gas Alarm
Systems for details of your nearest service centre.
4.6 Event logging
Gasmaster records alarms, faults and display panel
button activities in an Event Log. A maximum of 300
events are logged, after which data is over-written on
a first-in-first-out basis. This function provides a record
of all system activities which can be uploaded using
Gasmaster PC software at any time. The event log is
held in RAM (volatile memory), so in the event of a
complete power failure all data will be lost.
4.7 Service card
A card is fitted to the inside of the front cover for
logging service activity. It is recommended that this
card be filled in with the dates of services, and details
of any parts replaced.
4.8 Cleaning
If required, the outside of the Gasmaster case can be
cleaned by gently wiping with a damp cloth using a
mild soap solution only.
4. Maintenance