Over the next few pages you will find a detailed
description of the menu system. Use figure 3.4 as an
overall guide to locate menu items.
Gasmaster has five standard menus: Faults, Warnings,
View, Actions and Supervisor. Only the Supervisor menu
allows you to configure Gasmaster.
This section contains tables that list the menu items for
each menu and the available values.
See “Using the Control Panel in Supervisor Mode” on
page 21 for instructions on how to alter settings.
Note: The display only shows two lines of information
at a time. Use the Up
and Down
buttons to see
additional menu items or values.
Use Continue
to select choices and Back
to exit
menu.
Faults menu
(lists faults present on the system)
Menu system overview
Menu Item
Values (as shown on display)
Description
Fault codes
No faults
(end of list)
No faults are present
Faults
Measurement system failure!
Fatal fault, contact us.
1 or 2
Warning - Battery low
Input supply has failed and internal battery supply has
dropped to 22 volts.
4
Relay power supply fail
Power rail to the relays has failed and relays will no longer
operate. Contact us.
5
Main supply fail
Main supply has failed and the system is running on
batteries
6
NVM hardware fail
Fatal fault, contact us.
7
Loaded default settings
System has returned to standard configuration settings.
Re-configure using the Supervisor menu.
8
Common relay fail
Coil fault detected. Contact us.
9, 10, 11
Chan #1 relay fail
Channel relay coil fault detected. Contact us.*
12 to 19
ESU #1 stalled!
ESU sampling device has stopped.*
20 to 23
ESU #1 slow!
ESU sampling device has slowed.*
24 to 27
Chan #1 over range
Detector input signal is over 21.5 mA. Investigate cause at
detector taking necessary precautions as high gas levels
may be present.*
28 to 31
Chan #1 under range
Detector input signal is under 3 mA. Check detector.* If the
‘Interpret 2 mA’ command is set to Warning or Inhibit in the
channel configuration, this fault message will display when
the input signal drops below 1mA.
32 to 35
Chan #n: pellistor saver mode
mV pellistor type detector has been exposed to gas in
excess of 95%LEL. A 200-second timer will be applied, after
which the fault may be reset *
36-39
* #1 denotes the channel number and therefore may read #2, #3 or #4 on Gasmaster.
The fault codes are numbered to relate to a particular channel where appropriate (e.g. fault code 19 means there is a
fault on Channel 4 Level 2 alarm relay).