26
Warnings menu
(lists warnings present on the system)
Menu system overview
Menu Item
Values
(as shown on display)
Description
Fault codes
No
warnings
(end of list)
No warnings are present.
Warnings
Supervisor mode
System configurations may be changed.
1
Global inhibit
All input channels are inhibited.
2
Testing audio visual alarm
Audible visual outputs will be driven.
3
Service/calibration due
Service or calibration interval has expired.
4
Common relay forced
Common alarm or fault relays are being forced to
their ‘alarm’ state.
5, 6, 7
Main Supply Fail
Main supply has failed and the system is running on
batteries
8
Detector #1 stabilising
Detector is currently in its stabilisation or reset
period*, (see page 30).
9, 17, 25, 33
Detector #1 input low
Detector input signal is between 1 and 3 mA.* Only
applies when the ‘Interpret 2 mA’ command is set to
Warning in the channel configuration.
10, 18, 26, 3
Detector #1 initiated
inhibit
A 2 mA inhibit signal has been received from
a detector.* Only applies when the ‘Interpret 2
mA’ command is set to Inhibit in the channel
configuration.
11, 19, 27, 35
Chan #1 inhibited
Input channel is in an inhibit state*
12, 20, 28, 36
Chan #1 input simulated
Channel input is being forced in Test mode.*
13, 21, 29, 37
Chan #1 output forced
Channel analogue output is being forced in Test
mode.*
14, 28, 30, 38
Chan #1 relay forced
Channel alarm relay is being forced in Test mode.*
15, 16, 23, 24
31, 32, 39, 40
Chan#1 pellistor saver
disabled
Pellistor saver mode has been disabled, the sensor
may be damaged if exposed to gas concentrations
above 100%LEL.
41, 42, 43, 44
* #1 denotes the channel number and therefore may read #2, #3 or #4 on Gasmaster.