Assembly instructions for fitters /
Reducing the charging current – Switch 2
Assembly instructions for fitters/
Remote control of charger via enable port
FUSE 2AT
M
CP PP
Fuse/RCCB FB
Contactor FB
Contactor control
Line (L)
Neutral (N)
Protec
ti
ve earth (PE)
Type 2 outlet
1 2 3 4 5 6
DataLink
E-Meter
Ext. charge control
open=on, close=o
ff
*) -
see info below
SW2
SW1
Remote control
A -
B +
A -
B +
Max charging Factory default
current (A) 16A
Factory default
SW3
Reducing the charging current – Switch 2
(figure 11)
Depending on the size of the fuse, overload may occur, primarily at the property's meter
fuse. The wallbox's charging current can be reduced using the switches on the circuit
board. The supply voltage must be broken before the charging current is reduced.
The wallbox is equipped with a port, where charging can be activated and deactivated.
The charger's remote control capability allows charging to be controlled externally
through, for example, a relay outlet such as a timer or other superordinate control unit.
Charging can be verified in two ways:
•
Activate charging by opening the circuit between the Remote Control connection
blocks. This option is the factory setting.
•
Activate charging by closing the circuit between the Remote Control connection
blocks.
Remote control of charger via enable port
DIP Switch settings
Charging is activated at
DIP Switch SW1.4
Open circuit
ON (Factory setting)
Closed circuit
OFF
Remote control –
see table below
(figure 12)