Climatic & Environment constraints
Operating temperature (with derating)
-25°C to +55°C
(3)
Storage temperature
-25°C to +60°C
Relative humidity
RH
10% to 95%
Installation altitude
Alt
2 000 m
Max
Internal DC output protection
Hardware and software short circuit protection
Yes
Software and Hardware over voltage protection
adjustable
+10% max
Over temperature protection
-
70
°C
Reverse polarity protection
Yes
DC output Contactor
Yes (2 poles)
Rated Current Fuse (output)
I
FUSE
125 A
Galvanic isolation
V
input / output
5200 V
DC
Max time for DC line discharge < 60V
T
<60V
1 s
Internal AC output protection
Inrush current
230A during 100 µs
30A during following second
Short circuit Socket I²t
A²s
75 000
Circuit breaker for AC circuit
50A curve C
Max time for DC line discharge < 60V
T
<60V
1 s
Embedded Insulation device of charger module
Response time (tan)
< 3sec. for asymmetrical fault
< 62sec. for symmetrical fault
Self test time
At power on and every 60s during charge
Internal resistance Ri of the measuring circuit
1.5Mohms permanent
750Kohms continuous measurement
300Kohms during simultaneous switching measurement
Measurement method
Continuous and switching measurement resistor method
Measuring current Im
< 1,4mA at RF=0
Measurement range (Ran)
20Kohms…300Kohms
Relative uncertainty
±15%
Line L+/L- Voltage (Un)
DC 150V…530V
System leakage capacity Ce
≤
1µF : response value (Ran) and time (tan) are not guaranteed for
capacity above 1µF
Parallelization
Do not connect the insulation monitor device (IMD) in parallel!
Response value (Ran) and time (tan) are not guaranteed.
EN
6