background image

spray mode until it is switched to either 
the OFF switch or the BAKE switch is 
pushed. The SPRAY mode provides 120 
volt to the PLC, which in turn supplies 
120 volt to starter SM2 and the 
temperature controller in the remote 
control panel. SM2 is present for 
controlling an exhaust motor. As soon as 
SM2 is energized, 120 v power is 
supplied to SM1 through the PLC after a 
timed delay. SM1 is provided for 
controlling the motor contained within 
the air make up unit and a timed delay 
will still be present to delay start up. 
SM1 allows 120 volt power to be 
supplied to the green light for the supply 
motor and the burner thru the PLC. Both 
are located on the remote control panel. 
 
When the burner switch is set to the 
winter position, 120 volt  power is 
provided to the PLC, which supplies 120  
volt power to the gas train power circuit. 
When the burner switch is in the summer 
position the gas train power circuit will 
not be energized in the SPRAY mode. 
 

Bake 
( Models 99270 ) 

 
With the OFF switch on and the SPRAY 
switch on Placing the BAKE switch in 
BAKE provides 120 volt power through 
the PLC internal bake timer. For the 
99270 deluxe model the bake timer is 
located on the face of the remote panel. 
 
The BAKE switch supplies 120 volt 
power to the PLC in the main control 
panel, which begins the delay cycle. The 
purge timer should be set for a minimum 
of 3 minutes. At the completion of the 
delay cycle, 120 volt power is supplied 
to the change over damper solenoid. In 
turn, the change over damper is opened 
pneumatically releasing the damper air 

valve. When the damper valve is 
released, the change over damper 
solenoid is energized, the compressed air 
solenoid is de-energized. The lighting 
circuit is also removed from 120 volt 
supply. This drops out the lighting and 
compressed air source for spray. The 
PLC supplies 120 volt power to the gas 
train power circuit. 
 
In bake the PLC places the temperature 
controller in the second set point or 2SP. 
This is the bake mode setting.
At the end of the programmed bake time, 
whether 1 or 999 minutes, the PLC 
initiates the shut down mode.    
 

Shut Down 

 
The bake timer initiates the timed shut 
down mode. The supply to the change 
over solenoid is also restablished. The 
change over damper closes. The lights 
come back on and the temperature 
controller returns to the first set position, 
SP.  If burner switch is in the summer 
position, the PLC will shut off the gas 
train circuit. 
 
At the end of the timed cool down cycle 
(1 to 10 minutes), all functions of the 
unit will shut down completely, with the 
exception of the lights. The PLC 
interrupts the 120 volt power to the 
exhaust fan, the intake fan and the 
burner circuit. The lights in the booth 
will remain “on” until switched off. The 
PLC will hold the unit in the “off” status 
until the power is interrupted to the 
system by pushing the OFF switch to 
“off” and back “on”. 
 

Bake 
( Models 99273 and 99275 ) 

 

 

8

Summary of Contents for 99270

Page 1: ......

Page 2: ...other flammable vapors and liquids in open containers in the vicinity of this appliance is hazzardous WARNING Improper installation adjustment alteration service or maintenance can cause property dam...

Page 3: ...and it s proper firing rate are shown on the appliance rating plate Electrical characteristics are shown on the rating plate as well If the need for a change in fuel type occurs the manufacturer must...

Page 4: ...install fan belts and sheaves Adjust for proper belt tension Proper tension is achieved when the belt can be depressed 1 2 with moderate pressure at mid point between the motor and the fan sheves The...

Page 5: ...nit is for use with a paint spray booth The use of two 120 volt 20 ampere circuits for lighting will need to be supplied to the unit when used in conjunction with a paint spray booth The motor require...

Page 6: ...lt DC signal in the flame guard device During initiation there is a 10 second trial period At the end of this time if there is no flame in the pilot area the flame guard will lock out the burner syste...

Page 7: ...ves that the valve is closed before allowing electrical power to continue through the gas train circuit Cabin Pressure Control System Model 99270 A manual adjust lever is provided at the exhaust press...

Page 8: ...control transformer When the power switch and spray switch are actuated power is given to the motors If either exhaust fan motor starter or the supply motor starter trips out on overload the respectiv...

Page 9: ...or a minimum of 3 minutes At the completion of the delay cycle 120 volt power is supplied to the change over damper solenoid In turn the change over damper is opened pneumatically releasing the damper...

Page 10: ...troller returns to the first set position SP When the burner switch is in the summer position the PLC shuts off the gas train circuit At the end of the timed cool down cycle 1 to 10 minutes all functi...

Page 11: ...nifold modulating valve If the Flame Guard Device does not receive proof of flame in the burner within 10 seconds the pilot solenoid and the ignition transformer will be de energized The Flame Guard D...

Page 12: ...burner will not start if the temperature across the burner is below 20 deg F 4 Adjust high fire setting by viewing gas meter at the test port on the burner manifold manual gas valve Set the temperatur...

Page 13: ...should be replaced annually 3 Blower wheel should be periodically inspected for build up of dust or dirt and cleaned if necessary 4 Annually check the burner and components The flame rod should be cha...

Page 14: ...at 40 60 PSI TEMPERATURE DOES NOT Outside air temperature is Increase set point on RISE BURNER GREEN greater than set point Temperature control Reset LIGHT IS ON High limit is tripped Low gas high li...

Reviews: