background image

gas tube for tightness and good 
connection. Make sure that the air flow 
sensor tube is tight and well connected. 
 
4. Perform gas pressure test at test port 
on inlet manual gas valve and assure that 
the maximum pressure listed on the unit 
information tag is not exceeded. In 
addition, check that there is enough gas 
pressure and capacity for burner size. 
 
5. Check all gas lines and gas manifold 
for leaks. 
 
6. Double check all electrical 
connections to the unit. 
 

Start Up 

 
1. Bump start the motors and check for 
proper rotation. Correct rotation if 
necessary. 
 
2. Connect amp probe to motor circuits 
and turn unit on. Document amperages 
for each power leg and date. Assure that 
motors are within their motor plate 
amperage ratings. Leave documentation 
in the control panel and send copy with 
warranty information to manufacturer. 
 
3. Install gas pressure gauges on the on 
manual gas valves of the gas train. After 
unit is up and running, turn burner on. 
While waiting for gas train safety to 
complete it’s cycle, turn burner manifold 
manual gas valve off.  When ignition 
sequence has completed and pilot flame 
is present, use the pilot orifice on the gas 
manifold to adjust the pilot flame to 
approximately four (4) inches in height, 
or the size of a fist. If a freeze thermostat 
is install for extremely cold climates,      
( below -20 deg. F. ) the burner will not 
start if the temperature across the burner 
is below –20 deg. F. 

 
4. Adjust high fire setting by viewing 
gas meter at the test port on the burner 
manifold manual gas valve.   
 
Set the temperature controller on the 
remote control panel to the manual 
setting and set output to 100 %. Open 
the burner manifold manual gas valve 
long enough to acquire reading and close 
the valve. The pressure should be  4.2”  
WC minimum and should not exceed 
5.2” WC maximum. Adjust regulator if 
necessary and test again. Set temperature 
controller back to 0.0 % output and open 
output manual gas valve. 
 
5.  Adjust the burner ribbon with the 
temperature control in the manual setting 
and set to 0.0 % output. Viewing the 
burner, adjust the zero increase 
potentiometer in the top of the gas 
manifold modulating motor.  Adjust the 
zero increase until a small flame is 
ribboning across the bottom of the 
burner trough.  When adjustment is 
correct, set temperature control back to 
the auto setting.  Increase and decrease 
the temperature setting on the 
temperature control to check for proper 
operation. 
 
6. Set the bake timer to 5 minutes. On 
99270  model push the SPRAY and the 
BAKE switches. On the 99273 and 
99275 units set the OFF/SPRAY/BAKE  
switch to the BAKE position. Wait for 
change over to occur. After 3 minutes 
the dampers should change over to 
recycle. When the bake timer times out, 
the cool down cycle will begin. The 
entire unit should shut down after the 
cool down cycle is complete. 
 
7. Test air through- put and change 
sheaves if necessary. 

 

11

Summary of Contents for 99270

Page 1: ......

Page 2: ...other flammable vapors and liquids in open containers in the vicinity of this appliance is hazzardous WARNING Improper installation adjustment alteration service or maintenance can cause property dam...

Page 3: ...and it s proper firing rate are shown on the appliance rating plate Electrical characteristics are shown on the rating plate as well If the need for a change in fuel type occurs the manufacturer must...

Page 4: ...install fan belts and sheaves Adjust for proper belt tension Proper tension is achieved when the belt can be depressed 1 2 with moderate pressure at mid point between the motor and the fan sheves The...

Page 5: ...nit is for use with a paint spray booth The use of two 120 volt 20 ampere circuits for lighting will need to be supplied to the unit when used in conjunction with a paint spray booth The motor require...

Page 6: ...lt DC signal in the flame guard device During initiation there is a 10 second trial period At the end of this time if there is no flame in the pilot area the flame guard will lock out the burner syste...

Page 7: ...ves that the valve is closed before allowing electrical power to continue through the gas train circuit Cabin Pressure Control System Model 99270 A manual adjust lever is provided at the exhaust press...

Page 8: ...control transformer When the power switch and spray switch are actuated power is given to the motors If either exhaust fan motor starter or the supply motor starter trips out on overload the respectiv...

Page 9: ...or a minimum of 3 minutes At the completion of the delay cycle 120 volt power is supplied to the change over damper solenoid In turn the change over damper is opened pneumatically releasing the damper...

Page 10: ...troller returns to the first set position SP When the burner switch is in the summer position the PLC shuts off the gas train circuit At the end of the timed cool down cycle 1 to 10 minutes all functi...

Page 11: ...nifold modulating valve If the Flame Guard Device does not receive proof of flame in the burner within 10 seconds the pilot solenoid and the ignition transformer will be de energized The Flame Guard D...

Page 12: ...burner will not start if the temperature across the burner is below 20 deg F 4 Adjust high fire setting by viewing gas meter at the test port on the burner manifold manual gas valve Set the temperatur...

Page 13: ...should be replaced annually 3 Blower wheel should be periodically inspected for build up of dust or dirt and cleaned if necessary 4 Annually check the burner and components The flame rod should be cha...

Page 14: ...at 40 60 PSI TEMPERATURE DOES NOT Outside air temperature is Increase set point on RISE BURNER GREEN greater than set point Temperature control Reset LIGHT IS ON High limit is tripped Low gas high li...

Reviews: