In areas where the ambient temperature 
can fall below –20 deg. F, it is 
recommended that a low temperature 
limit control (freeze thermostat ) be 
installed (not provided by Garmat 
USA®. The low temperature control 
shall be installed in series with the high 
limit switch in the gas train safety 
circuit.  
 
 

High Gas Pressure Switch  
( Models 99273 and 99275 )  

 
This component is on the gas manifold 
and will disconnect electrical power to 
the gas train circuit before reaching the 
flame guard device. In the event that 
more than 21” WC of gas pressure enters 
the gas manifold at this point, the switch 
will disconnect the power and will need 
to be manually reset. 
 

Low Gas Pressure Switch  
( Models 99273 and 99275 )  

 
This component is on the gas manifold 
and will disconnect electrical power to 
the gas train circuit before reaching the 
flame guard device. In the event that less 
than 3” WC of gas pressure enters the 
gas manifold or pressure drops below 
this point, the switch will disconnect the 
power and will automatically reset when 
pressure is restored.` 
 

Proof Of Closure Switch  
( Models 99273 and 99275 )  

 
This switch is mounted directly under 
one of the blocking valves on the gas 
train and is linked to the valve actuator 
and proves that the valve is closed 
before allowing electrical power to 
continue through the gas train circuit. 
 

 

Cabin Pressure Control System 

 

 ( Model 99270 )  
 

A manual ¼ adjust lever is provided at 
the exhaust pressure damper. A slack 
tube manometer is provided for 
montering the cabin pressure. 
 

( Models 99273 and 99275 ) 
 

The remote control panel contains a 
photohelic gauge. This gauge is 
displayed on the face of the remote panel 
and controls the air pressure within the 
cabin. This gauge is adjustable using the 
two orange needles visible on the face of 
the gauge. The gauge operates a 
modulating motor attached to exhaust 
pressure damper. Opening the cabin will 
cause loss of cabin air pressure. 

 
PROGRAMMABLE LOGIC 
CONTROLLER ( PLC ) 
( All Models) 

 
The electrical panel contains a 
programmable logic controller ( PLC ). 
The PLC controls all of the automatic 
functions of the control sequence 
including flash-off time duration, bake 
time duration and cool down time 
duration. Bake time duration is set at the 
remote panel on the 99270 deluxe, 
99273,  99275 models. On the model 
99270 the bake timer is internal in the 
PLC. Flash-off time duration and cool 
down  time duration are  internal 
functions of the PLC and are set at the 
factory. The factory  setting of the flash-
off time duration is three minutes and for 
the cool down time duration is ten 
minutes. These time durations can be 
reset by your authorized local authorized 
distributor. 

 

6

Summary of Contents for 99270

Page 1: ......

Page 2: ...other flammable vapors and liquids in open containers in the vicinity of this appliance is hazzardous WARNING Improper installation adjustment alteration service or maintenance can cause property dam...

Page 3: ...and it s proper firing rate are shown on the appliance rating plate Electrical characteristics are shown on the rating plate as well If the need for a change in fuel type occurs the manufacturer must...

Page 4: ...install fan belts and sheaves Adjust for proper belt tension Proper tension is achieved when the belt can be depressed 1 2 with moderate pressure at mid point between the motor and the fan sheves The...

Page 5: ...nit is for use with a paint spray booth The use of two 120 volt 20 ampere circuits for lighting will need to be supplied to the unit when used in conjunction with a paint spray booth The motor require...

Page 6: ...lt DC signal in the flame guard device During initiation there is a 10 second trial period At the end of this time if there is no flame in the pilot area the flame guard will lock out the burner syste...

Page 7: ...ves that the valve is closed before allowing electrical power to continue through the gas train circuit Cabin Pressure Control System Model 99270 A manual adjust lever is provided at the exhaust press...

Page 8: ...control transformer When the power switch and spray switch are actuated power is given to the motors If either exhaust fan motor starter or the supply motor starter trips out on overload the respectiv...

Page 9: ...or a minimum of 3 minutes At the completion of the delay cycle 120 volt power is supplied to the change over damper solenoid In turn the change over damper is opened pneumatically releasing the damper...

Page 10: ...troller returns to the first set position SP When the burner switch is in the summer position the PLC shuts off the gas train circuit At the end of the timed cool down cycle 1 to 10 minutes all functi...

Page 11: ...nifold modulating valve If the Flame Guard Device does not receive proof of flame in the burner within 10 seconds the pilot solenoid and the ignition transformer will be de energized The Flame Guard D...

Page 12: ...burner will not start if the temperature across the burner is below 20 deg F 4 Adjust high fire setting by viewing gas meter at the test port on the burner manifold manual gas valve Set the temperatur...

Page 13: ...should be replaced annually 3 Blower wheel should be periodically inspected for build up of dust or dirt and cleaned if necessary 4 Annually check the burner and components The flame rod should be cha...

Page 14: ...at 40 60 PSI TEMPERATURE DOES NOT Outside air temperature is Increase set point on RISE BURNER GREEN greater than set point Temperature control Reset LIGHT IS ON High limit is tripped Low gas high li...