OUTDOOR VENTILATION AIR 
( All Models ) 

 
Outdoor air must be ducted to the air 
make up unit inlet when unit is installed 
inside of a building. This ducting shall 
be no smaller than 30” square or the 
equivalent in crossectional surface area 
in diameter of round ducting. Bends or 
transitions are not recommended and 
length should be kept to less than 5 
meters or 16.5 feet. If bends or 
transitions are required, turning vanes 
are recommended. 
 

LINE PRESSURE TEST  
( All Models ) 

 
The make up unit and its inlet manual 
gas valve must be disconnected from gas 
supply piping during any pressure 
testing above 21” WC. The air make up 
unit must be isolated from the gas supply 
system by closing the manual gas valve 
up stream of the regulator on the inlet of 
the gas manifold. 
 

PROPER SEQUENCE OF 
OPERATION 

 
The Garmat

®

 USA Inc. air make up unit 

can be ordered with several different 
usage options. To simplify the sequence 
of operations, all four available options 
will be covered. 
 
There are four modes of operation: 
Power On, Run or Spray, Recycle or 
Bake and Shut Down. 
 

Power On  
( Models 99273 & 99275 ) 
 

The three phase voltage supplies power 
to the control transformer. The 120, and 
24 volt is connected through the control 
transformer. When the power switch and   
spray switch are actuated, power is given 
to the motors. If either exhaust fan motor 
starter or the supply motor starter trips 
out on overload the respective motor and 
make up unit operations will cease until 
respective motor starter is reset.  Both 
control voltages are protected with 
breakers in the main electrical panel. 
 
A 120 volt jumper is provided in the 
main control panel which can be 
connected through a NC contact on a 
micro switch used for a fire suppression 
system. 
 
When The NC contact is opened, the 120 
volt control supply is removed from the 
circuit and the entire unit shuts down. 
The EM (Emergency stop) switch on the 
remote control panel does the same. 
Rotating the EM  switch reconnects the 
120 volt supply, unless the fire system 
has not been reset.    
 
The green light will illuminate when the 
EM switch is rotated clockwise. The 120 
volt control  power is connected through 
the EM switch in the remote control 
panel.  If either motor starter trips out on 
overload, a red light will illuminate for 
the respective motor and make up unit 
operations will cease until respective 
motor starter is reset.  Both control 
voltages are protected with breakers in 
the main control panel. 
 

Run or Spray 
( Models 99270 and 99270-E ) 

 
With the OFF switch on the spray cycle 
can be started by pushing the SPRAY 
switch. The air make up will run in the 

 

7

Summary of Contents for 99270

Page 1: ......

Page 2: ...other flammable vapors and liquids in open containers in the vicinity of this appliance is hazzardous WARNING Improper installation adjustment alteration service or maintenance can cause property dam...

Page 3: ...and it s proper firing rate are shown on the appliance rating plate Electrical characteristics are shown on the rating plate as well If the need for a change in fuel type occurs the manufacturer must...

Page 4: ...install fan belts and sheaves Adjust for proper belt tension Proper tension is achieved when the belt can be depressed 1 2 with moderate pressure at mid point between the motor and the fan sheves The...

Page 5: ...nit is for use with a paint spray booth The use of two 120 volt 20 ampere circuits for lighting will need to be supplied to the unit when used in conjunction with a paint spray booth The motor require...

Page 6: ...lt DC signal in the flame guard device During initiation there is a 10 second trial period At the end of this time if there is no flame in the pilot area the flame guard will lock out the burner syste...

Page 7: ...ves that the valve is closed before allowing electrical power to continue through the gas train circuit Cabin Pressure Control System Model 99270 A manual adjust lever is provided at the exhaust press...

Page 8: ...control transformer When the power switch and spray switch are actuated power is given to the motors If either exhaust fan motor starter or the supply motor starter trips out on overload the respectiv...

Page 9: ...or a minimum of 3 minutes At the completion of the delay cycle 120 volt power is supplied to the change over damper solenoid In turn the change over damper is opened pneumatically releasing the damper...

Page 10: ...troller returns to the first set position SP When the burner switch is in the summer position the PLC shuts off the gas train circuit At the end of the timed cool down cycle 1 to 10 minutes all functi...

Page 11: ...nifold modulating valve If the Flame Guard Device does not receive proof of flame in the burner within 10 seconds the pilot solenoid and the ignition transformer will be de energized The Flame Guard D...

Page 12: ...burner will not start if the temperature across the burner is below 20 deg F 4 Adjust high fire setting by viewing gas meter at the test port on the burner manifold manual gas valve Set the temperatur...

Page 13: ...should be replaced annually 3 Blower wheel should be periodically inspected for build up of dust or dirt and cleaned if necessary 4 Annually check the burner and components The flame rod should be cha...

Page 14: ...at 40 60 PSI TEMPERATURE DOES NOT Outside air temperature is Increase set point on RISE BURNER GREEN greater than set point Temperature control Reset LIGHT IS ON High limit is tripped Low gas high li...