background image

 

3-1-618    Page 7 

SECTION 2 
OPERATING AND MAINTENANCE INSTRUCTIONS 

 

INSTALLATION 

LOCATION - 

Pump should be located as close to the 

fluid supply as possible.  A short and direct suction 
line will improve pump performance and reduces the 
possibilities of cavitation.  Whenever possible, 
adequate space should be provided around the pump 
to permit easy inspection and adjustment.  Particular 
attention should be given to the space required for 
removal and installation of the gear reducer, 
eccentric, etc. 

The drive must be accurately aligned.  Pump must be 
properly leveled and securely fastened to a 
foundation or base.  The pump must have a positive 
suction head.  Refer to page 19 for NPSH 
requirements.  Maximum allowable temperature of 
the fluid being pumped is 180

°

 F (82

°

 C).  The 

maximum allowable suction pressure is 75 PSI.  Any 
application with suction pressures over 75 PSI must 
be approved in writing by Gardner Denver Inc. 
Engineering Department. 

SUCTION PIPING

 - Suction pipe (or hose if used) 

should be the full size of suction opening.  If, for any 
reason, the suction line is of greater length than 
usual, the next larger size should be used.  Suction 
line should slope up towards the pump at a uniform 
grade so that air pockets are eliminated.  Suction line 
must be air tight as any air leaking into the line will 
reduce the volumetric efficiency of the pump.  If it is 
necessary to have bends in the suction line, they 
should have long radius sweeps. 

Refer to page 18 for recommended suction piping 
system.  All piping must be supported independently 
of the pump to insure that no strain is imposed in the 
pump by misalignment or improperly fitted pipe. 

 

 

PRESSURE RELIEF VALVE – 

The pump must be 

protected from excessive discharge pressure by a 
pressure relief valve.  This valve must be installed as 
near to the pump discharge manifold as possible. 

 

The pressure relief valve should be set to operate at 
approximately 1.1 to 1.25 times the discharge 
pressure, depending on the relief valve 
manufacturer’s recommendations, but this setting 
MUST NOT exceed adjoining system equipment 
rated pressure capabilities. The relief valve must be 
sized to accept the full pump flow per the valve 
manufacturer’s instructions. 
 
When the pump is equipped with a shear pin type 
pressure relief valve, use only the shear pin specified 
in the relief valve   manufacturer’s instructions.  Do 
not use allen wrenches for shear pins, or hammer on 
the shear bar stem, or shear bar slot.  For complete 
installation and maintenance instructions refer to the 
relief valve manufacturer’s catalog and/or instruction 
manual. 

 
 

                       

   

WARNING 

 

 
Never install a shutoff valve in the line 
between the pressure relief valve and the 
pump cylinder, as pumping against a 
closed valve could produce pressures 
sufficient to cause property damage and/or 
serious personal injury or death. 

                     

   

DANGER 

 

 
Improper use or maintenance of pressure 
relief valves can cause excessive pressure 
which may result in property damage 
and/or serious personal injury or death. 

                     

   

DANGER 

 

 
Never install a shutoff valve in the line 
between the pressure relief valve and the 
pump cylinder, as pumping against a 
closed valve could produce pressures 
sufficient to cause property damage and/or 
serious personal injury or death. 

Summary of Contents for GD-250

Page 1: ...GARDNER DENVER 3 1 618 Version 1 January 2011 TRIPLEX PISTON PUMP 5 STROKE MODEL GD 250 WELL SERVICE OPERATING AND SERVICE MANUAL Rental Pump Supplied By...

Page 2: ...ed distributor service technicians are factory trained and skilled in pump maintenance and repair They are ready to respond and assist you by providing fast expert maintenance and repair services For...

Page 3: ...operation and minimum downtime DANGER Danger is used to indicate the presence of a hazard which will cause severe personal injury death or substantial property damage if the warning is ignored WARNIN...

Page 4: ...tions 7 Crankcase Oil Requirements 16 Gardner Denver Horizontal Pump Recommended System Layout for Proper Performance 16 Net Positive Suction Head Required NPSHR at Fluid Cylinder Suction Connection w...

Page 5: ...ting and Cleaning Danger Notice 5 6 Hydraulic Puller Danger Notice 2 INSTALLATION AND OPERATING INSTRUCTIONS SECTION 2 7 Lifting and Moving Equipment Danger Notice 2 Location 7 Lubrication Packing 12...

Page 6: ...or Temperature Correction Char 21 Wedge Puller Danger Notice 2 LIST OF ILLUSTRATIONS Figure Description Page Figure 1 View of the Eccentric thru the Hood Opening Step 1 18 Figure 2 View of the Eccent...

Page 7: ...g and service manuals should be readily available for operator and maintenance personnel use Read and follow all the precautions and instructions contained in these manuals If any of these documents a...

Page 8: ...e handle to avoid losing control of the hammer while swinging and striking Carefully swing the hammer to avoid striking themselves another person and objects other than the targeted wedge Avoid swingi...

Page 9: ...o lift a pump package unit subassemblies or individual components and you observe the equipment is tilting or appears unbalanced lower the equipment and adjust the lifting device to eliminate these im...

Page 10: ...han every six months if pressures above 2 500 PSI are used in the discharge system or if corrosive flammable or hot over 110 F fluids are being pumped Before starting the pump the first time and perio...

Page 11: ...s must be taken to avoid possible personal injury death and or equipment damage from explosion fire or burns HIGH PRESSURE LIQUID JETTING BLASTING AND CLEANING Pressure or flow directing devices often...

Page 12: ...tion These components should all be tagged with their tested pressure capabilities together with the date testing was performed Always be aware of the pressure level in the system and never connect an...

Page 13: ...supported independently of the pump to insure that no strain is imposed in the pump by misalignment or improperly fitted pipe PRESSURE RELIEF VALVE The pump must be protected from excessive discharge...

Page 14: ...f care is taken to stay within the listed temperature ranges Straight weight oils are also ideal in pumps used indoors when ambient temperatures are controlled The oil level in the pump should be chec...

Page 15: ...the crankcase Drain all water accumulation from the bottom of crankcase Check all nuts and screws and tighten if necessary Fill crankcase with oil of proper grade to proper level Quantity on the data...

Page 16: ...th a valve seat puller Wipe the tapered surface of the valve seat and pump valve deck in the fluid cylinder with a clean cloth Lower the seat into the port taper and then lift slightly and drop If the...

Page 17: ...nd rust in the stuffing box pilot bores in the frame Install the packing in the box Place a new gasket in the stuffing box groove The gasket chamfered edge must face out to prevent gasket pinching whe...

Page 18: ...e placed over a lock pin which has been inserted in a lock pin hole in the gland When using self adjusting packing tighten the gland nut firmly after assembling it metal to metal with the stuffing box...

Page 19: ...ot contaminate the crankcase oil CROSSHEAD AND PINS Crossheads can be removed through the oil stop head openings Crossheads are equipped with straight pins secured on each end by setscrews and locknut...

Page 20: ...re Tighten oil stop head gland to prevent seal movement while pump is in operation These oil stop head seals are nonadjustable When crankcase oil leakage occurs past seals the seals should be replaced...

Page 21: ...the crankcase the oil and filter should be changed Drain and clean out the crankcase before putting in new oil Replace the oil stop head seals before running the pump We recommend oil stop head seals...

Page 22: ...e or grade used A crankcase heater and or an oil heat exchanger may be needed to meet these requirements Crankcase capacity is 12 gallons 45 4 liters WARNING Failure to follow these lubrication requir...

Page 23: ...y into tank outlet 4 A short straight suction line is preferred from the tank to the pump If this is not possible use as few bends as possible and use long radius elbows The smallest portion of the li...

Page 24: ...3 1 618 Page 18 FIGURE 1 STEP 1 FIGURE 2 STEP 2...

Page 25: ...3 1 618 Page 19 FIGURE 3 STEP 3 FIGURE 4 STEP 4...

Page 26: ...d minimum plunger sizes Interpolate between NPSH curves for each plunger size NPSHR is defined at a 3 flow drop below maximum capacity Added suction head above that shown by the curves must be provide...

Page 27: ...3 1 618 Page 21 CORRECTION CHART FOR TEMPERATURE OR VISCOSITY...

Page 28: ...0 592 64 60 20 45 40 3 106 0 35 9 0 3 9 67 45 800 176 81 00 677 73 80 23 35 35 2 120 0 39 9 8 4 1 74 50 900 198 91 00 762 83 00 26 30 31 3 135 0 41 10 7 4 3 82 58 1000 220 100 7 896 92 10 29 20 28 2 1...

Page 29: ...mbly 2 Valve propped open 2 Remove prop 3 Pump cavitating 3 See Cavitation Fluid Knock or Hammer problem 4 Fluid leakage 4 Replace fluid end seals 5 Erroneous gauge reading 5 Recalibrate or replace ga...

Page 30: ...13 Multiple pumps operating in 13 Use a suction stabilizer phase on each pump Separate lines may also be needed Suction or Discharge Line Vibration 1 Line s not supported 1 Install supports or hangers...

Page 31: ...il stop head packing 2 Replace packing 3 Oil level too high in 3 Reduce oil level crankcase 4 Excessive crosshead wear 4 Replace crosshead 5 Pressure in crankcase 5 Clean or replace air breather Oil S...

Page 32: ...temperature 5 Lube oil pump failure 5 Replace oil pump 6 Low oil level in sump 6 Check oil level frequently and add oil as required 7 Contaminated oil in sump 7 Check oil condition frequently 8 Cavita...

Page 33: ...ad Pin 2 0015 2 0020 50 838 50 851 Bore in Connecting Rod Bushing for Eccentric 10 499 10 505 266 675 266 827 Crosshead Pin Diameter 2 0005 2 0000 50 8127 50 8000 Bore in Crosshead for Pin 2 0010 2 00...

Page 34: ...Service Department Telephone 800 682 9868 FAX 217 223 1581 For Domestic parts information Contact Gardner Denver Fluid Transfer Division 2200 South Prospect Oklahoma City OK 73129 Telephone 405 677 57...

Reviews: