Message
Action needed
POWER FAILURE
The power to the compressor unit has been turned off and back on.
Press [STOP/RESET] and select an operating mode.
SHORTED THERM
The controller has detected a shorted connection to thermistor: (A)
airend discharge or (B) separator. This normally indicates a faulty
connection (e.g. wire strands touching) at the controller connector 7;
check and correct the connection. This could also be indicating a
damaged wire or thermistor probe.
SHORTED XDUCER
Signal voltage has exceeded approximately 4.6 volts at transducer: (A)
final discharge or (B) reservoir. This may indicate a loose connection of
the black wire to the transducer or a defective transducer. Check
connections, or replace transducer if necessary.
WATER PRESS
120 volts has been removed from terminal 7 of the terminal strip. This is
normally shipped jumpered directly to terminal 9, but the jumper may be
removed to add a field installed shutdown switch. Reset the external
switch.
ZERO XDUCER
Signal voltage has fallen too low at transducer: (A) final discharge or (B)
reservoir. This error is usually the result of the transducers being
improperly zeroed. Disconnect the air lines to the transducers and follow
the procedure indicated in the adjustment instructions. This shutdown
for transducer B may also be the result of reverse compressor rotation.
Check connections, or replace transducer if necessary.
Summary of Contents for AUTO SENTRY-ES+
Page 19: ...13 9 653 Page 15 Figure 1 3 WIRING DIAGRAM 216EAP546 B Ref Drawing Page 1 of 2...
Page 20: ...13 9 653 Page 16 216EAP546 B Ref Drawing Page 2 of 2...
Page 21: ...13 9 653 Page 17 Figure 1 4 WIRING DIAGRAM 304EBH546 C Ref Drawing Page 1 of 2...
Page 22: ...13 9 653 Page 18 304EBH546 C Ref Drawing Page 2 of 2...
Page 23: ...13 9 653 Page 19 Figure 1 5 WIRING DIAGRAM 301EAQ546 B Ref Drawing Page 1 of 2...
Page 24: ...13 9 653 Page 20 301EAQ546 B Ref Drawing Page 2 of 2...