background image

Scope of Work/Materials 

 
13850 (28 31 00) - 5 
 
Bid No.041818-Installation of New Fire Alarm System at Adams Elementary School 

c. 

Prepare using AutoCAD. 

d. 

Prepare to scale 1/8 inch = 1’-0”, unless otherwise required by the Architect or 

Engineer. 

e. 

Show equipment and device locations. 

f. 

Show wiring information in point-to-point format. 

g. 

Show conduit routing, if required by the AHJ. 

3. 

Title Block:  Provide on each sheet and include, at a minimum, the following: 
a. 

Project name. 

b. 

Project address. 

c. 

Sheet name. 

d. 

Sheet number. 

e. 

Scale of drawing. 

f. 

Date of drawing. 

g. 

Revision dates, if applicable. 

4. 

Control Panel:  Provide sheet that details exterior and interior views of control panel and 
clearly shows associated wiring information. 

5. 

Annunciator Panels:  Provide sheet that details exterior and interior views of annunciator 
panels and clearly shows associated wiring information. 

 

E. 

Certification:  Submit with equipment submittals and shop drawings, letter of certification from 

Gamewell-FCI

, indicating proposed engineered system distributor is an authorized 

representative in good standing of the equipment supplied.  Include a copy of at least two (2) 
certified technician E3 system training certificates. 

 

F. 

Project Record Drawings: 
1. 

Submit complete project record drawings within 14 calendar days after acceptance test. 

2. 

Project record drawings shall be similar to shop drawings but revised to reflect changes 
made during construction. 

 

G. 

Operation and Maintenance Manuals: 
1. 

Submit complete operation and maintenance manuals within 14 calendar days after 
acceptance test. 

2. 

Operation and maintenance manuals shall be similar to equipment submittals but revised 
to reflect changes made during construction. 

3. 

Include 

factory’s standard installation and operating instructions. 

 

1.6 

QUALITY ASSURANCE 

 

A. 

Codes and Standards: 
1. 

NFPA:  System shall comply with the following NFPA codes and standards: 
a. 

NFPA 12. 

b. 

NFPA 13. 

c. 

NFPA 15. 

d. 

NFPA 16. 

e. 

NFPA 16A. 

f. 

NFPA 70. 

g. 

NFPA 72. 

h. 

NFPA 90A. 

 

i.       NFPA 90B When smoke control is required by code. 

Summary of Contents for E3 Series

Page 1: ...Data Interchange 2 RS 485 standard defining the electrical characteristics of drivers and receivers for use in balanced digital multipoint systems B National Fire Protection Association NFPA 1 NFPA 12...

Page 2: ...ary power failure until alarm signal is processed and recorded 7 Network Node Communications a Communicated between panels on single pair of copper wires or fiber optic cables b To enhance system surv...

Page 3: ...ean control by event programming including as a minimum AND OR NOT and Timer functions 6 Control Panels Capability to accept firmware upgrades via connection with laptop computer without requirement o...

Page 4: ...uding elevator recall elevator power shutdown door lock release door holder release HVAC unit shutdown smoke evacuation system activation and stair pressurization fan activation 5 Bill of Material OWN...

Page 5: ...bmittals and shop drawings letter of certification from Gamewell FCI indicating proposed engineered system distributor is an authorized representative in good standing of the equipment supplied Includ...

Page 6: ...of devices circuits zones and changes to system operation and custom label changes for devices or zones 4 System structure and software shall place no limit on type or extent of software modification...

Page 7: ...ly Module PM 9 with batteries 3 80 Character LCD Display LCD E3 4 Intelligent Loop Main Board Interface ILI MB E3 or ILI95 MB E3 5 Optional Intelligent Loop Supplemental Interface ILI S E3 or ILI95 S...

Page 8: ...or and control modules Display shall be liquid crystal type LCD clearly visible in dark and under all light conditions 3 Panel shall contain 4 functional keys a Alarm Acknowledge b Trouble Acknowledge...

Page 9: ...cuits on SLC or NAC circuits disarrangement in system wiring failure of microprocessor or any identification module or system ground faults shall activate this trouble circuit Trouble signal shall be...

Page 10: ...ull 4100 event history log supporting local and network functions If a main processor or network node is lost the entire log shall be accessible at any other Loop Interface board This shall be demonst...

Page 11: ...e alarm systems in accordance with NFPA 72 as it is impossible to test all functions and verify items such as annunciation with only 1 person 24 Signaling Line Circuits Each ILI MB E3 module shall pro...

Page 12: ...from 64 nodes to 122 nodes ANX SR Addressable Node Expander Single Ring will function in single 64 node systems 3 ANX shall provide a Ethernet Port for use in Systems Integration and for use with Eme...

Page 13: ...e Detectors Provide 2 status LEDs Both LEDs shall flash under normal conditions indicating detector is operational and in regular communication with control panel and both LEDs shall be placed into st...

Page 14: ...trol panel send data to panel representing analog level of products of combustion F Intelligent Multi Criteria Acclimating Detectors MCS ACCLIMATE2F 1 Addressable device designed to monitor a minimum...

Page 15: ...1 The detector shall be comprised of four sensing elements including a photoelectric light scattering particulate sensor an electrochemical CO sensor a daylight filtered infrared IR sensor and solid...

Page 16: ...hange over air handling systems to help prevent rapid distribution of toxic smoke and fire gases throughout areas served by duct system 3 Duct Smoke Detectors Mounted Above Ceiling or Otherwise Obstru...

Page 17: ...D to blink latch on or latch off Flash under normal conditions indicating monitor module is operational and in regular communication with control panel P Addressable Dry Contact Monitor Modules MMI 10...

Page 18: ...module NAC Wire for Style Z or Style Y Class A B with up to 1 amp of inductive signal or 2 amps of resistive signal operation Relay coil shall be magnetically latched to reduce wiring connection requi...

Page 19: ...nel D NGA Network Graphic Annunciator 1 Main Menu a Configure allows Auto configuration of ILI MB S and NGA or ANX b Walk Drill enables Walk Test and Fire Drill function c I O Allows enable disable in...

Page 20: ...arm system devices control panels and remote annunciators in finished areas Flush mount or surface mount fire detection and alarm system devices control panels and remote annunciators in unfinished ar...

Page 21: ...anufacturer representative of Owner and fire department shall operate every installed device to verify proper operation and correct annunciation at control panel 3 Open signaling line circuits and not...

Reviews: