Scope of Work/Materials
13850 (28 31 00) - 19
Bid No.041818-Installation of New Fire Alarm System at Adams Elementary School
A.
Graphic Annunciator (Uses ANU-48 Serial Driver Board):
1.
Communicate to fire alarm control panel via EIA-485 (multi-drop) 2-wire communications
loop. Up to 16 annunciator drivers, each configured up to 48 points, shall be connected
per ILI-MB-E3.
3.
ANU-48: Provide interface to approved UL-listed graphic-style annunciator and provide
each of the features specified.
B.
Auxiliary Switch Module (ASM-16):
1.
Each ASM-16 has 16 programmable push-button switches.
2.
Each push-button switch has 3 associated status LEDs (red, yellow, and green),
configurable to indicate any combination of functions.
3.
Flexible switch configurations to allow auxiliary functions.
4.
Insert label to identify function of each switch and LEDs combination.
5. Provide capability to communicate with up to 16 ASM-16 modules locally, or up to 3,000
feet from the Control Panel.
D. NGA Network Graphic Annunciator
1 Main Menu
a. Configure allows Auto-configuration of ILI-MB-S and NGA or ANX.
b. Walk/Drill enables Walk Test and Fire Drill function.
c.
I/O Allows enable/disable input and output devices.
d. Clock system real-time clock.
e.
View system configuration information
f.
NGA log displays, stores, prints and clears the 4100 event history log.
g.
Service provides Network Query functions.
h. (More spec items
– Text messaging, custom logo, custom screensaver, max amount
of text on screen at one time)
E.
Horns:
1.
Operate on 24 VDC or with field-selectable outputs.
2.
Have two selectable tone options of temporal 3 and non-temporal continuous pattern.
3. Have at least 2 audibility options
F.
Strobes:
1.
Compliance: ADA and UL 1971.
2.
Maximum Pulse Duration: 0.2 second.
3.
Strobe Intensity: UL 1971.
4.
Flash Rate: UL 1971.
5.
Strobe Candela Rating: Determine by positioning selector switch on back of device.
G.
Horn/Strobes:
1.
Operate on 24 VDC
2.
Have two selectable tone options of temporal 3 and non-temporal continuous pattern.
3. Have at least 2 audibility options
4.
Maximum Pulse Duration: 0.2 second.
5.
Strobe Intensity: UL 1971.
6.
Flash Rate: UL 1971.