Scope of Work/Materials
13850 (28 31 00) - 12
Bid No.041818-Installation of New Fire Alarm System at Adams Elementary School
4.
An insertable label to identify function of each switch and LEDs combination.
5. Provide capability to communicate with up to 16 ASM-16 modules locally, or up to 3,000
feet from the Control Panel
H.
Graphic Annunciator (NGA): Optional 1/4 VGA, touch-screen annunciator with the following
characteristics:
1.
Custom Graphics: Panel shall permit uploading of custom bit-mapped graphic to display
screen. Graphic shall display when all systems are normal.
2.
Intuitive Functions: In alarm or trouble condition, annunciator shall display only
information pertaining to event, including control switches.
a.
Trouble Condition: Display shall indicate cause of trouble. Only controls available to
operator shall be Acknowledge and Reset functions.
b.
Alarm Condition: Display shall indicate cause of alarm. Only controls available to
operator shall be Acknowledge, Silence, and Reset functions.
I.
Addressable Node Expander (ANX):
1.
Addressable Node Expander shall provide interconnection between the Fire Alarm Control
Panel networks.
2.
ANX-MR-FO (Addressable Node Expander Multi-Ring with Fiber Optic connectors) and
ANX-MR-UTP (Addressable Node Expander Multi-Ring with Fiber Optic and Twisted Pair
connectors) shall expand the E3 Series network from 64 nodes to 122 nodes. ANX-SR
(Addressable Node Expander Single Ring) will function in single 64 node systems.
3. ANX shall provide a Ethernet Port for use in Systems Integration and for use with
Emergency Communication System (ECS) functions. The Ethernet port may also be used
to communicate with a graphic interface software.
J. Network Repeater Module (RPT-E3):
1.
Intelligent Network Interface shall provide interconnection and protection of remote INCC
Command Centers and Transponders. Repeater shall regenerate and condition token
passing, 625 K baud signal between units. Repeater shall be available in wire, or
wire/fiber configurations as determined by field conditions.
2.
Interface shall have jumper to allow selection of ground detection of wiring when used in
wire mode. Interface shall have integral LEDs to display current status of board.
3.
Fiber configurations shall use:
a. Multi-Mode ST-type connectors with a maximum attenuation of 8db with 62.5/125-micron
cable.
b. Single-Mode LC-style connector with a maximum attenuation of 30db with 9/125-micron
cable.
2.4
PRINTERS
A.
Printers: Automatic type, printing code, time, date, location, category, and condition.
1.
Provide hard-copy printout of all changes in status of system and time-stamp such
printouts with current time-of-day and date.
2.
Standard carriage with 80 characters per line.
3.
Use standard pin-feed paper.
4.
Enclose in separate enclosure suitable for placement on desktop or table.
5.
Communicate with control using interface complying with EIA-232-D.
6.
Power: 120 VAC at 60 Hz.