Scope of Work/Materials 

 
13850 (28 31 00) - 3 
 
Bid No.041818-Installation of New Fire Alarm System at Adams Elementary School 

2. 

Local Piezo-Electric Signal in Control Panel:  Sound at a pulse rate. 

3. 

80-Character LCD Display:  Indicate all information associated with fire alarm condition, 
including type of alarm point and its location within protected premises. 

4. 

Historical Log:  Record information associated with fire alarm control panel condition, 
along with time and date of occurrence. 

5. 

System output programs assigned via control-by-event equations to be activated by 
particular point in alarm shall be executed, and the associated system outputs (alarm 
notification appliances and/or relays) shall be activated. 

 

6.      Strobes flash synchronized continuously. 
7. 

Audible devices sound continuous Temporal pattern until system is reset. 

 

E. 

Fire Alarm System Functionality

:  Owner Provided

 

1. 

Install a complete, electrically supervised distributed, Style 7 networked 
analog/addressable fire alarm and control system, with analog initiating devices. 

2. 

Fire Alarm System: 
a. 

Incorporate E3 Series multiprocessor-based control panels, with Intelligent Loop 

Interface ILI-MB-E3 and RPT-E3 repeater modules communicating over peer-to-peer 
token ring network with capacity of up to 64 nodes. 

3. 

Each ILI-MB-E3 SLC module:  Incorporate 2 Signaling Line Circuits (SLC), with capacity to 
support up to 159 analog addressable detectors and 159 addressable modules per SLC. 

4. 

All data transmits over single pair of wires or fiber optic cable. 

5. 

Each Network Node:  Incorporate Boolean control-by-event programming, including as a 
minimum AND, OR, NOT, and Timer functions. 

6. 

Control Panels:  Capability to accept firmware upgrades via connection with laptop 
computer, without requirement of replacing microchips. 

7. 

Network: 
a. 

Based on peer-to-peer token ring technology operating at 625 K baud, using Style 7 

configuration. 

b. 

Capability of using twisted-pair wiring, pair of fiber optic cable strands up to 200 

microns, or both, to maximize flexibility in system configuration. 

8. 

Each Network Node: 
a. 

Capability of being programmed off-line using Windows-based software utilized by 

fire alarm system manufacturer.  Capability of being downloaded by connecting 
laptop computer into any other node in system.  Systems that require system 
software to be downloaded to each transponder at each transponder location shall 
not be acceptable. 

b. 

Capability of being grouped with any number of additional nodes to produce a 

“Region”, allowing that group of nodes to act as 1, while retaining peer-to-peer 
functionality.  Systems utilizing 

“Master/Slave” configurations shall not be 

acceptable. 

c. 

C

apability of annunciating all events within its “Region” or annunciating all events 

from entire network, on front panel LCD without additional equipment. 

9. 

Each SLC Network Node:  Capability of having integral DACT (digital alarm communicator 
transmitter) that can report events in either its region, or entire network to single central 
station monitoring account. 

10.  Each Control Panel:  Capability of storing its entire program and allow installer to activate 

only devices that are installed during construction, without further downloading of system. 

12.  Password Protection:  Each system shall be provided with 4 levels of password protection 

with up to 16 passwords. 

Summary of Contents for E3 Series

Page 1: ...Data Interchange 2 RS 485 standard defining the electrical characteristics of drivers and receivers for use in balanced digital multipoint systems B National Fire Protection Association NFPA 1 NFPA 12...

Page 2: ...ary power failure until alarm signal is processed and recorded 7 Network Node Communications a Communicated between panels on single pair of copper wires or fiber optic cables b To enhance system surv...

Page 3: ...ean control by event programming including as a minimum AND OR NOT and Timer functions 6 Control Panels Capability to accept firmware upgrades via connection with laptop computer without requirement o...

Page 4: ...uding elevator recall elevator power shutdown door lock release door holder release HVAC unit shutdown smoke evacuation system activation and stair pressurization fan activation 5 Bill of Material OWN...

Page 5: ...bmittals and shop drawings letter of certification from Gamewell FCI indicating proposed engineered system distributor is an authorized representative in good standing of the equipment supplied Includ...

Page 6: ...of devices circuits zones and changes to system operation and custom label changes for devices or zones 4 System structure and software shall place no limit on type or extent of software modification...

Page 7: ...ly Module PM 9 with batteries 3 80 Character LCD Display LCD E3 4 Intelligent Loop Main Board Interface ILI MB E3 or ILI95 MB E3 5 Optional Intelligent Loop Supplemental Interface ILI S E3 or ILI95 S...

Page 8: ...or and control modules Display shall be liquid crystal type LCD clearly visible in dark and under all light conditions 3 Panel shall contain 4 functional keys a Alarm Acknowledge b Trouble Acknowledge...

Page 9: ...cuits on SLC or NAC circuits disarrangement in system wiring failure of microprocessor or any identification module or system ground faults shall activate this trouble circuit Trouble signal shall be...

Page 10: ...ull 4100 event history log supporting local and network functions If a main processor or network node is lost the entire log shall be accessible at any other Loop Interface board This shall be demonst...

Page 11: ...e alarm systems in accordance with NFPA 72 as it is impossible to test all functions and verify items such as annunciation with only 1 person 24 Signaling Line Circuits Each ILI MB E3 module shall pro...

Page 12: ...from 64 nodes to 122 nodes ANX SR Addressable Node Expander Single Ring will function in single 64 node systems 3 ANX shall provide a Ethernet Port for use in Systems Integration and for use with Eme...

Page 13: ...e Detectors Provide 2 status LEDs Both LEDs shall flash under normal conditions indicating detector is operational and in regular communication with control panel and both LEDs shall be placed into st...

Page 14: ...trol panel send data to panel representing analog level of products of combustion F Intelligent Multi Criteria Acclimating Detectors MCS ACCLIMATE2F 1 Addressable device designed to monitor a minimum...

Page 15: ...1 The detector shall be comprised of four sensing elements including a photoelectric light scattering particulate sensor an electrochemical CO sensor a daylight filtered infrared IR sensor and solid...

Page 16: ...hange over air handling systems to help prevent rapid distribution of toxic smoke and fire gases throughout areas served by duct system 3 Duct Smoke Detectors Mounted Above Ceiling or Otherwise Obstru...

Page 17: ...D to blink latch on or latch off Flash under normal conditions indicating monitor module is operational and in regular communication with control panel P Addressable Dry Contact Monitor Modules MMI 10...

Page 18: ...module NAC Wire for Style Z or Style Y Class A B with up to 1 amp of inductive signal or 2 amps of resistive signal operation Relay coil shall be magnetically latched to reduce wiring connection requi...

Page 19: ...nel D NGA Network Graphic Annunciator 1 Main Menu a Configure allows Auto configuration of ILI MB S and NGA or ANX b Walk Drill enables Walk Test and Fire Drill function c I O Allows enable disable in...

Page 20: ...arm system devices control panels and remote annunciators in finished areas Flush mount or surface mount fire detection and alarm system devices control panels and remote annunciators in unfinished ar...

Page 21: ...anufacturer representative of Owner and fire department shall operate every installed device to verify proper operation and correct annunciation at control panel 3 Open signaling line circuits and not...