27
All copying, even partial, of this manual is strictly forbidden.
RG66007970 - Rev 01
13 eleCTRICal DaTa anD COnneCTIOnS
- The maximum electrical input is the mains electricity that must be available in order for the unit to work�
- The maximum current absorption refers to the current that will trigger the internal safety devices of the unit�
It is the maximum current allowed in the unit� This value may never be exceeded; it must be used as a reference for determining the size of the
power supply line and the related safety devices (refer to the wiring diagram supplied with the units)�
MPI DC
08 M
010 M
014
018
023
029
Maximum power input
kW
4,1
5,6
7,1
10,7
10,8
21,9
Maximum current absorption
A
16
26,6
20
22
28,5
43
Starting absorbed current
A
10
10
10
10
10
10
Fan motor rated power
kW
0,24
0,14
0,14
0,14
0,14
0,14
Fan motor rated current
A
1,03
0,64
0,64
0,64
0,64
0,64
Pump motor rated power
kW
0,14
0,48
0,65
0,65
0,65
0,65
Pump motor rated current
A
0,58
2,7
3
3
3
3
Power supply
V/f/Hz
230/1/50
400/3n/50
Auxiliary power supply
V/f/Hz
230/1/50
Power cables
mm
2
4
4
6
6
10
10
PCD connecting cables
mm
2
AWG22
AWG22
AWG22
AWG22
AWG22
AWG22
PCDS connecting cables
mm
2
1
1
1
1
1
1
Safety fuse F
A
20
20
25
25
32
32
Circuit breaker Il
A
20
20
25
25
40
40