background image

25

All copying, even partial, of this manual is strictly forbidden.

RG66007970 - Rev 01

12 

WaTeR CIRCUIT

When setting up the water circuit of the unit, it is advisable to follow the directions below and in any case comply with local or national regulations�
Connect the pipes to the chiller using flexible couplings to prevent the transmission of vibrations and to compensate thermal expansions�

It is recommended to install the following components on the pipes:

 

temperature and pressure indicators for routine maintenance and monitoring of the unit� Checking the pressure on the water side will enable you to verify 
whether the expansion tank is working efficiently and to promptly detect any water leaks within the equipment� 

 

Traps on incoming and outgoing pipes for temperature measurements, which can provide a direct reading of the operating temperatures� 

-  

 

Regulating valves (gate valves) for isolating the unit from the water circuit�

 

Metal mesh filter (supplied), with a mesh size no greater than 1 mm, to be fitted on the inlet pipe to protect the exchanger from scale or impurities 

present in the pipes.

 

Air vent valves, to be placed at the highest points of the water circuit for the purpose of bleeding air� The internal pipes of the unit are fitted with small 
air vent valves for bleeding the unit itself� This operation may only be carried out when the unit is disconnected from the power supply�

 

Drainage valve and, where necessary, a drainage tank for emptying out the equipment for maintenance purposes or when the unit is taken out of serv-
ice at the end of the season� A 1” drainage valve is provided on the optional water buffer tank: this operation may only be carried out when the unit is 
disconnected from the power supply�

It is of fundamental importance that the incoming water supply is hooked up to the connection marked “Water Inlet”�
otherwise the evaporator would be exposed to the risk of freezing since the antifreeze thermostat would not be able to perform its function; moreover the 
reverse cycle would not be respected in the cooling mode, resulting in additional risks of malfunctioning�

The dimensions and position of plumbing connections are shown in the dimension tables at the end of the manual�

The water circuit must be set up in such a way as to guarantee that the nominal flow rate of the water supplied to the evaporator remains constant (+/- 15%) 
in all operating conditions�
A standard feature of MPI  DC  units is a device for controlling the flow rate (flow switch or differential pressure switch) in the water circuit in the immediate 
vicinity of the evaporator�

12.1 

WaTeR COnTenT WIThIn The SySTeM anD ChaRGInG OF eXPanSIOn TanK

In models without buffer tank it is necessary to assure that the content of water within the system does not fall below 4�5 litres/kW in the case of heat pump 
models� This level is necessary to prevent the water temperature from falling below the indoor unit enabling threshold during defrost cycles�

n.B. kW in reference to rated capacity

The expansion tank is pre-charged to a pressure of 1�5 bars, sufficient for systems with a maximum height difference (H in the figure at the side) of 13 metres�
For greater height differences, refer to the table below in order to adjust the charging pressure of the expansion tank accordingly�
In no case should you exceed the maximum height difference Hmax = 35 m�

 leGenD

h

 

Height difference of system

p

i

 

Charging pressure of expansion tank

C

max

  Maximum system water content

Models

(m)

p

i

 

(bar)

C

max

 

(l)

MPI DC 08-029

<13

1,5

145

15

1,7

133

20

2,2

105

25

2,7

77

30

3,1

49

Summary of Contents for MPI DC 08

Page 1: ...MPI DC 08 kW 29 kW R410A eco Technical MANUAL FOR CHILLERS AND HEAT PUMPS GB CHILLERS AND HEAT PUMPS DC INVERTER...

Page 2: ...sors brazed plate heat exchangers liquid receivers pipes control and safety valves which are individually provided where required with certification in accordance with current directives the category...

Page 3: ...data are reported on the rating label in this page The label shows the following data Series and size of the unit Date of manufacture Main technical data Manufacturer The label is applied on the unit...

Page 4: ...equipped with an automatically controlled oil heating system to avoid oil dilution by the refrigerant when the compressor is stopped The compressor motor is a permanent magnets brushless alternating...

Page 5: ...automatically regulates the fan speed further limiting the noise emissions of the unit during nighttime operation and under partial load conditions FINNED BLOCK HEAT EXCHANGER Made of 8mm diameter cop...

Page 6: ...pressure switch fan compartment 5 Automatic air vent valve 6 Expansion tank fan compartment 7 Buffer tank accessory 8 4 way valve MPI DC H 9 Electronic expansion valves 10 Water safety valve 11 Liqui...

Page 7: ...switch fan compartment 5 Automatic air vent valve 6 Expansion tank fan compartment 7 Buffer tank accessory 8 4 way valve MPI DC H 9 Electronic expansion valves 10 Water safety valve 11 Liquid receiver...

Page 8: ...ure switch fan compartment 5 Automatic air vent valve 6 Expansion tank fan compartment 7 Buffer tank accessory 8 4 way valve MPI DC H 9 Electronic expansion valves 10 Water safety valve 11 Liquid rece...

Page 9: ...or 0 Model size 1 4 Operation H Water chiller C Heat pump H Supply voltage 0 Standard 400 3N 50 0 Single phase M Refrigerant A R410A high efficiency A Revision A Initial A Expansion valve A Electronic...

Page 10: ...pply V ph Hz 230 1 50 400 3N 50 400 3N 50 400 3N 50 400 3N 50 Rated cooling capacity kW 10 6 14 3 18 2 22 9 29 1 Total power input kW 3 35 4 78 7 63 7 77 12 3 EER rated capacity 3 16 2 99 2 39 2 95 2...

Page 11: ...Total power input with pump kW 2 8 3 6 5 3 8 2 8 3 12 9 Rated heating capacity kW 8 89 11 5 15 7 21 6 24 6 33 7 Total power input in heating mode kW 2 81 3 56 4 96 7 48 7 86 11 7 COP rated power 3 16...

Page 12: ...07 2 53 1 14 2 37 1 22 14 9 3 27 0 87 3 11 0 94 2 95 1 00 2 78 1 07 2 62 1 15 2 46 1 23 15 10 3 38 0 87 3 21 0 93 3 05 1 00 2 89 1 07 2 71 1 15 2 55 1 23 16 11 3 49 0 86 3 32 0 93 3 15 1 00 2 98 1 07...

Page 13: ...95 14 9 4 62 1 43 4 41 1 53 4 20 1 62 3 98 1 72 3 75 1 83 3 49 1 95 15 10 4 79 1 43 4 56 1 52 4 35 1 62 4 12 1 72 3 88 1 83 3 61 1 95 16 11 4 95 1 42 4 72 1 52 4 50 1 61 4 26 1 71 4 01 1 83 3 74 1 95...

Page 14: ...57 5 74 2 73 5 42 2 91 14 9 7 13 2 16 6 84 2 30 6 56 2 43 6 26 2 57 5 94 2 74 5 61 2 92 15 10 7 37 2 15 7 07 2 29 6 78 2 42 6 47 2 57 6 15 2 74 5 81 2 92 16 11 7 62 2 15 7 31 2 29 7 01 2 42 6 69 2 57...

Page 15: ...2 1 22 14 9 3 21 0 87 3 05 0 94 2 89 1 00 2 73 1 07 2 57 1 15 2 41 1 23 15 10 3 31 0 87 3 15 0 93 2 99 1 00 2 83 1 07 2 66 1 15 2 50 1 23 16 11 3 42 0 86 3 25 0 93 3 09 1 00 2 92 1 07 2 75 1 15 2 58 1...

Page 16: ...5 1 83 3 31 1 95 14 9 4 53 1 43 4 33 1 53 4 12 1 62 3 91 1 72 3 67 1 83 3 42 1 95 15 10 4 69 1 43 4 47 1 52 4 27 1 62 4 04 1 72 3 80 1 83 3 54 1 95 16 11 4 85 1 42 4 63 1 52 4 41 1 61 4 18 1 71 3 93 1...

Page 17: ...2 2 91 14 9 7 00 2 16 6 72 2 30 6 44 2 43 6 14 2 57 5 83 2 74 5 51 2 92 15 10 7 23 2 15 6 94 2 29 6 65 2 42 6 35 2 57 6 03 2 74 5 70 2 92 16 11 7 48 2 15 7 17 2 29 6 87 2 42 6 56 2 57 6 24 2 74 5 90 2...

Page 18: ...14 20 3 75 15 70 3 74 40 45 8 11 3 78 9 37 3 90 11 40 4 03 13 80 4 11 15 30 4 12 45 50 7 94 4 03 9 19 4 19 11 20 4 37 13 50 4 48 14 90 4 51 MPI DC 010 H Rated data at intermediate frequency 25 30 5 1...

Page 19: ...45 18 60 8 17 21 10 8 31 25 10 8 44 30 20 8 55 33 20 8 58 45 50 18 40 8 91 20 80 9 05 24 70 9 21 29 70 9 33 32 60 9 39 MPI DC 023 H Rated data at intermediate frequency 25 30 12 80 4 47 14 50 4 42 17...

Page 20: ...within the range defined by the operating limits Attempting to operate the units beyond these limits could cause irreparable damage to the units themselves 8 1 Operating limits in chiller mode Outlet...

Page 21: ...nd water outlet temperature CPF PT Corrective coefficient of cooling heating capacity CPA Correction coefficient of electrical input CQw Correction coefficient of water flow rate C pw1 Correction coef...

Page 22: ...PORTATA l h PERDITE kPa MPIDC018 MPIDC023 MPIDC029 MPI DC 08 014 MPI DC 018 029 All copying even partial of this manual is strictly forbidden RG66007970 Rev 01 10 PRESSURE DROPS 10 1 PRESSURE DROPS WA...

Page 23: ...000 10000 12000 p kPa Qw l h MPI DC 010 029 MPI DC 08 All copying even partial of this manual is strictly forbidden RG66007970 Rev 01 10 PRESSURE DROPS 10 2 PRESSURE DROPS OF Y FILTER The diagram show...

Page 24: ...0 6000 6400 PORTATA l h PREVALENZA kPa MPIDC018 MPIDC023 MPIDC029 MPI DC 018 029 All copying even partial of this manual is strictly forbidden RG66007970 Rev 01 11 AVAILABLE HEAD OF THE UNIT The diagr...

Page 25: ...when the unit is disconnected from the power supply It is of fundamental importance that the incoming water supply is hooked up to the connection marked Water Inlet Otherwise the evaporator would be...

Page 26: ...TER CIRCUIT PLUMBING DIAGRAMS MPI DC evaporator and pump MPI DC evaporator pump and tank LEGEND VS Safety valve EV Evaporator PD Differential pressure switch MA Water pressure gauge VAS Air vent valve...

Page 27: ...refer to the wiring diagram supplied with the units MPI DC 08 M 010 M 014 018 023 029 Maximum power input kW 4 1 5 6 7 1 10 7 10 8 21 9 Maximum current absorption A 16 26 6 20 22 28 5 43 Starting abso...

Page 28: ...and PCDS remote control panel Note Should the unit go into an alarm status a voltage of 24V will be present on the terminals of the electric control panel where an interface with a voltage free contac...

Page 29: ...DIMENSIONS MPI DC 08 Legend 1 Water inlet 1 female 2 Water outlet 1 female 3 Safety valve discharge outlet provided with rubber ring holder 4 Water supply male optional tap 5 Water drainage female 6 P...

Page 30: ...L DIMENSIONS MPI DC 10 18 Legend 1 Water inlet 1 female 2 Water outlet 1 female 3 Safety valve discharge outlet provided with rubber ring holder 4 Water supply male optional tap 5 Water drainage femal...

Page 31: ...IMENSIONS MPI DC 23 29 Legend 1 Water inlet 1 female 2 Water outlet 1 female 3 Safety valve discharge outlet provided with rubber ring holder 4 Water supply male optional tap 5 Water drainage female 6...

Page 32: ...lease contact the manufacturer to check for feasibility In the design of the MPI DC series special care has been taken to minimise noise and vibrations transmitted to the ground Even greater insulatio...

Page 33: ...anual is strictly forbidden RG66007970 Rev 01 15 Installation clearance requirements MPI DC 10 18 MPI DC 23 29 COIL PLUMBING CONNECTION SIDE ELECTRIC CONTROL BOARD COIL SIDE COIL PLUMBING CONNECTION S...

Page 34: ...fan air flow A prevalent wind blowing from a direction opposite to the fan air flow will reduce the maximum air temperature to a lower value than specified in the operating limits A wind blowing in t...

Page 35: ...35 All copying even partial of this manual is strictly forbidden RG66007970 Rev 01 NOTES...

Page 36: ...Wolf Schweiz AG Dorfstrasse 147 CH 8802 Kilchberg Telefon 41 43 500 48 00 Fax 41 43 500 48 19 info wolf klimatechnik ch www wolf klimatechnik ch...

Reviews: