6 PeRFORManCeS
6.3
heaTInG CaPaCITIeS MPI DC-h
Tbs
1
Air inlet temperature (dry bulb)
Tw in/out
Water inlet/outlet temperature
PT
Heating capacity
Pa
Total power input including pump
Rh
Relative humidity
Tbs
1
/ Rh
-5 °C / 90 %
0 °C / 90 %
7 °C / 88 %
15 °C / 80 %
20°C / 70 %
Tw in
Tw out
PT
Pa
PT
Pa
PT
Pa
PT
Pa
PT
Pa
[°C]
[°C]
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
MPI DC 018 h
Rated data at maximum frequency
25
30
17,00
5,90
18,80
6,05
22,6
6,21
27,4
6,22
30,4
6,15
30
35
16,60
6,43
18,50
6,56
22,3
6,71
25,9
8,35
29,7
6,77
35
40
16,40
7,04
18,30
7,15
21,9
7,30
26,5
7,42
29,0
7,44
40
45
16,10
7,71
18,00
7,83
21,4
7,98
25,9
8,35
28,3
8,19
45
50
16,00
8,46
17,70
8,57
21,1
8,76
25,3
8,94
27,6
9,01
MPI DC 018 h
Rated data at intermediate frequency
25
30
10,20
3,44
11,70
3,53
14,00
3,57
17,10
3,53
19,10
3,46
30
35
9,93
3,71
11,40
3,78
13,70
3,84
16,70
3,84
18,60
3,80
35
40
9,67
4,01
11,20
4,08
13,40
4,15
16,40
4,18
18,00
4,18
40
45
9,54
4,36
11,00
4,43
13,20
4,50
16,00
4,56
17,50
4,57
45
50
9,36
4,76
10,70
4,82
12,80
4,91
15,40
4,98
16,90
5,01
MPI DC 018 h
Rated data at minimum frequency
25
30
2,95
1,58
3,37
1,60
4,07
1,60
5,03
1,55
5,26
1,92
30
35
2,87
1,66
3,30
1,67
4,00
1,68
4,90
1,65
5,16
1,99
35
40
2,80
1,75
3,22
1,76
3,91
1,77
4,76
1,76
5,07
2,06
40
45
2,74
1,85
3,15
1,86
3,80
1,88
4,61
1,88
4,98
2,14
45
50
2,69
1,96
3,08
1,98
3,70
1,99
4,47
2,01
4,89
2,22
MPI DC 023 h
Rated data at maximum frequency
25
30
20,00
6,84
22,30
6,74
25,80
6,69
31,50
6,63
34,80
6,60
30
35
19,40
7,11
21,90
7,15
25,40
7,18
31,10
7,18
34,30
7,18
35
40
19,00
7,58
21,50
7,68
25,00
7,68
30,60
7,77
34,00
7,84
40
45
18,60
8,17
21,10
8,31
25,10
8,44
30,20
8,55
33,20
8,58
45
50
18,40
8,91
20,80
9,05
24,70
9,21
29,70
9,33
32,60
9,39
MPI DC 023 h
Rated data at intermediate frequency
25
30
12,80
4,47
14,50
4,42
17,20
4,37
21,00
4,32
23,00
4,30
30
35
12,50
4,66
14,10
4,66
16,70
4,66
20,50
4,66
22,50
4,64
35
40
12,20
4,94
13,90
4,98
16,40
5,02
20,10
5,04
23,00
5,04
40
45
12,00
5,29
13,50
5,35
16,20
5,41
19,60
5,47
21,70
5,48
45
50
11,80
5,72
13,30
5,79
15,80
5,88
19,30
5,94
21,20
5,96
MPI DC 023 h
Rated data at minimum frequency
25
30
4,74
2,43
5,34
2,40
6,38
2,37
7,78
2,34
9,11
2,32
30
35
4,62
2,51
5,23
2,50
6,26
2,49
7,63
2,47
8,39
2,96
35
40
4,51
2,61
5,12
2,62
6,13
2,63
7,49
2,62
8,27
3,07
40
45
4,42
2,75
5,03
2,77
6,02
2,79
7,32
2,79
8,15
3,18
45
50
4,35
2,92
4,95
2,95
5,91
2,97
7,16
2,98
8,02
3,29
MPI DC 029 h
Rated data at maximum frequency
25
30
27,20
9,73
29,60
9,67
34,90
9,62
36,90
9,60
46,50
9,51
30
35
26,40
10,22
29,80
10,32
34,40
10,36
40,70
12,87
45,90
10,43
35
40
26,00
10,97
29,40
11,07
33,90
11,27
41,70
11,37
45,30
11,47
40
45
25,60
11,87
29,00
12,07
33,40
12,27
40,70
12,87
44,40
12,57
45
50
25,60
13,07
28,80
13,27
33,00
13,47
40,20
13,67
43,80
13,77
MPI DC 029 h
Rated data at intermediate frequency
25
30
16,80
5,62
18,70
5,58
22,20
5,52
26,90
5,45
29,70
5,41
30
35
16,30
5,89
18,30
5,92
21,80
5,93
26,50
5,91
29,10
5,90
35
40
15,90
6,28
17,90
6,35
21,40
6,42
25,90
6,45
28,50
6,45
40
45
15,50
6,77
17,60
6,86
21,00
6,96
25,30
7,03
27,80
7,05
45
50
15,30
7,37
17,30
7,47
20,60
7,59
24,80
7,68
27,30
7,72
MPI DC 029 h
Rated data at minimum frequency
25
30
4,72
2,40
5,33
2,38
6,39
2,34
7,75
2,30
9,02
2,27
30
35
4,60
2,48
5,21
2,48
6,25
2,47
7,60
2,44
8,32
2,94
35
40
4,49
2,59
5,11
2,60
6,12
2,61
7,46
2,60
8,19
3,04
40
45
4,40
2,74
5,01
2,75
6,00
2,77
7,29
2,77
8,06
3,15
45
50
4,33
2,91
4,93
2,93
5,89
2,95
7,12
2,96
7,93
3,26