6 PeRFORManCeS
6.1
COOlInG CaPaCITIeS MPI DC-h
Tbs
1
Air inlet temperature (dry bulb)
Tw in/out
Water inlet/outlet temperature
PF
Cooling capacity
Pa
Total power input including pump
Tbs
1
20
25
30
35
40
45
Tw in
Tw out
PF
Pa
PF
Pa
PF
Pa
PF
Pa
PF
Pa
PF
Pa
[°C]
[°C]
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
MPI DC 023 h
Rated data at maximum frequency
10
5
24,40
6,47
23,30
7,00
22,20
7,59
21,10
8,26
19,90
9,01
18,60
9,84
11
6
25,10
6,49
24,10
7,01
22,90
7,62
21,80
8,30
20,60
9,07
19,20
9,89
12
7
25,90
6,49
24,80
7,04
23,60
7,65
22,50
8,34
21,20
9,11
19,90
9,93
13
8
26,60
6,50
25,50
7,06
24,40
7,69
23,20
8,37
21,90
9,16
20,50
10,00
14
9
27,40
6,52
26,30
7,08
25,52
7,72
23,90
8,41
22,60
9,20
21,20
10,03
15
10
28,30
6,54
27,20
7,10
25,90
7,75
24,60
8,47
23,30
9,24
21,80
10,10
16
11
29,20
6,54
28,00
7,13
26,70
7,77
25,40
8,50
24,00
9,29
22,50
10,13
17
12
30,00
6,57
28,80
7,14
27,50
7,80
26,10
8,54
24,70
9,35
23,20
10,20
MPI DC 023 h
Rated data at intermediate frequency
10
5
16,40
4,09
15,70
4,39
15,10
4,73
14,30
5,10
13,50
5,53
12,70
5,99
11
6
16,90
4,09
16,20
4,40
15,60
4,73
14,80
5,12
14,00
5,54
13,20
6,01
12
7
17,50
4,09
16,80
4,40
16,10
4,74
15,30
5,13
14,40
5,56
13,60
6,03
13
8
18,00
4,09
17,30
4,40
16,60
4,75
15,80
5,14
14,90
5,57
14,10
6,05
14
9
18,60
4,09
17,80
4,41
17,10
4,76
16,30
5,16
15,40
5,59
14,50
6,07
15
10
19,10
4,09
18,40
4,41
17,70
4,76
16,80
5,16
15,90
5,61
15,00
6,09
16
11
19,70
4,09
19,00
4,41
18,20
4,78
17,30
5,18
16,40
5,63
15,50
6,12
17
12
20,40
4,10
19,60
4,42
18,70
4,78
17,90
5,19
17,00
5,65
16,00
6,13
MPI DC 023 h
Rated data at minimum frequency
10
5
6,13
2,17
5,87
2,31
5,62
2,43
5,35
2,57
5,08
2,73
4,78
2,90
11
6
6,34
2,17
6,07
2,30
5,82
2,43
5,54
2,57
5,26
2,73
4,96
2,91
12
7
6,55
2,16
6,28
2,30
6,02
2,43
5,74
2,57
5,45
2,73
5,13
2,91
13
8
6,78
2,16
6,49
2,30
6,22
2,43
5,94
2,57
5,64
2,73
5,32
2,91
14
9
7,00
2,16
6,72
2,30
6,44
2,43
6,14
2,57
5,83
2,74
5,51
2,92
15
10
7,23
2,15
6,94
2,29
6,65
2,42
6,35
2,57
6,03
2,74
5,70
2,92
16
11
7,48
2,15
7,17
2,29
6,87
2,42
6,56
2,57
6,24
2,74
5,90
2,92
17
12
7,72
2,15
7,41
2,29
7,11
2,42
6,78
2,57
6,45
2,74
6,10
2,92
MPI DC 029 h
Rated data at maximum frequency
10
5
31,30
9,71
29,90
10,57
28,40
11,57
26,80
12,67
25,20
13,87
23,40
15,27
11
6
32,20
9,75
30,90
10,67
29,30
11,67
27,70
12,77
25,90
13,97
24,10
15,37
12
7
33,30
9,79
31,80
10,67
30,10
11,67
28,50
12,87
26,70
14,07
24,90
15,47
13
8
34,30
9,80
32,70
10,77
31,10
11,77
29,40
12,97
27,60
14,17
25,70
15,57
14
9
35,20
9,85
33,60
10,77
32,00
11,87
30,30
12,97
28,40
14,27
26,40
15,67
15
10
36,20
9,89
34,60
10,87
33,00
11,97
31,10
13,07
29,20
14,37
27,20
15,77
16
11
37,30
9,94
35,70
10,87
33,90
11,97
32,00
13,17
30,20
14,47
28,10
15,87
17
12
38,40
9,99
36,70
10,97
34,80
12,07
33,00
13,27
31,00
14,57
29,00
15,87
MPI DC 029 h
Rated data at intermediate frequency
10
5
20,90
5,27
20,00
5,67
19,10
6,14
18,10
6,68
17,10
7,28
16,00
7,94
11
6
21,50
5,27
20,60
5,68
19,70
6,17
18,70
6,70
17,70
7,31
16,60
7,97
12
7
22,20
5,26
21,30
5,70
20,30
6,18
19,30
6,73
18,20
7,34
17,10
8,01
13
8
22,90
5,26
22,00
5,70
21,00
6,20
19,90
6,76
18,80
7,37
17,70
8,03
14
9
23,60
5,26
22,60
5,72
21,60
6,22
20,60
6,77
19,40
7,40
18,20
8,07
15
10
24,30
5,26
23,30
5,72
22,30
6,23
21,20
6,80
20,00
7,42
18,80
8,10
16
11
25,00
5,26
24,00
5,73
23,00
6,26
21,80
6,82
20,70
7,45
19,40
8,13
17
12
25,70
5,27
24,70
5,74
23,60
6,28
22,50
6,85
21,30
7,49
20,00
8,17
MPI DC 029 h
Rated data at minimum frequency
10
5
6,15
2,15
5,89
2,28
5,63
2,41
5,36
2,55
5,08
2,71
4,78
2,89
11
6
6,35
2,14
6,08
2,28
5,82
2,41
5,55
2,55
5,25
2,71
4,95
2,89
12
7
6,56
2,13
6,29
2,27
6,02
2,40
5,73
2,55
5,44
2,71
5,12
2,89
13
8
6,78
2,13
6,50
2,27
6,22
2,40
5,93
2,55
5,63
2,71
5,31
2,89
14
9
7,00
2,12
6,71
2,26
6,43
2,40
6,13
2,55
5,82
2,71
5,49
2,89
15
10
7,22
2,11
6,93
2,26
6,64
2,39
6,34
2,54
6,01
2,71
5,68
2,90
16
11
7,46
2,10
7,15
2,25
6,86
2,39
6,54
2,55
6,22
2,71
5,87
2,90
17
12
7,69
2,10
7,38
2,25
7,08
2,39
6,76
2,54
6,42
2,72
6,06
2,90