4. Connect the AC supply mains to the black (Live/Hot) and white (Neutral) wires in
accordance with LifeSafetys installation manuals, NFPA section 70 and local authority
electrical codes.
5. Energize the Lifesafety FPO150 mains.
Note: A power lead is not provided with the kit.
6. Ensure all equipment operates correctly, both with mains power ON/batteries ON, and
with mains power OFF/batteries ON.
Battery Low alarm
The Battery Low system alarm will be triggered when the battery charge falls below 10.8 V.
If no battery is connected the Battery Low alarm will not activate. This output is connected to
Input 7 on the default configuration of the Primary 8In 4Out Board.
Mains Failure alarm
The Mains Failure system alarm will be triggered when the mains voltage falls below
approximately 90 V or when the mains voltage rises above approximately 250 V. This output
is connected to Input 8 on the default configuration on the Primary 8In 4Out Board.
Note: Both Battery Low alarm and Mains Failure alarm are sent as a system notification to the
customer via the Gallagher SMB app. These events are also visible in the Event History of the
controller in the SMB Configuration app.