![Galil Motion Control RIO-47 series
RIO-47100 User Manual Download Page 84](http://html1.mh-extra.com/html/galil-motion-control/rio-47-series-rio-47100/rio-47-series-rio-47100_user-manual_558776084.webp)
-422
This option allows the RIO to communicate via RS-422 instead of RS-232.
Pin
Description
Pin
Description
1
RTS-
6
RTS+
2
TXD-
7
TXD+
3
RXD-
8
RXD+
4
CTS-
9
CTS+
5
GND
Part number ordering example:
RIO-47100-422
-RTC
RIO models with
Expanded Memory
(See if your model does in Table 1.1) come standard with
some real time clock features. The –RTC option provides an extended feature set as shown
below in Table 6.1.
Real time clock
Expanded Memory
with -RTC option
RT providing hours, minutes, seconds
Yes
Yes
RY providing year, month, date, and day of the week
No
Yes
Settable via TIME protocol server (IH and RO commands)
Yes
Yes
Clock persists through RIO power loss
No
Yes
C No-power clock battery life
N/A
More than 1 week
1
Table 6.1: Real time clock features and expanded -RTC features set.
1
Time till failure pending at the time of publication
Part number ordering example:
RIO-47122-RTC
-12V
This option allows for the RIO to be powered from a 10.5 to 15 VDC source (standard is 18 to 36
VDC). This option is only available for the RIO-471xx products. Contact Galil if this option is
needed on a RIO-472xx.
The RIO will no longer have the option to be powered over PoE with this modification.
Part number ordering example:
RIO-47120-12V
-2LSRC
If a RIO-471xx is ordered with the -2LSRC option then outputs 8-15 are configured to source
current. They will be capable of 5-24VDC with 25mA of current in a sourcing configuration. See
25mA Low Power Sourcing Outputs (LSRC) in Chapter 4 for more information.
Part number ordering example:
RIO-47100-(1HSRC,2LSRC)
-1LSNK/-1LSRC & -2LSNK/-2LSRC
These four options are only available on the RIO-472xx. By default the RIO-472xx has all 16 high
power outputs. These options allow either of the two banks of 8 outputs to be configured for low
power sinking or low power sourcing. For example, if output 0-7 need to be configured for low
power sourcing and outputs 8-15 need to be configured for high power sourcing the option
would be (1LSRC, 2HRSC). The circuits for low power sourcing and sinking will be the same as the
circuits for the low power outputs previously defined in Chapter 4.
Appendix ▫ 84 RIO-47xxx Rev. 1.0r