Water Counter Menu
Turn the selector to the "Water Counter" menu.
The upper row shows Water Counter No. 1
Move down until you reach Wtr.Counter Setup.
Enter the parameters as follows:
Subject
Example
Explanation
Puls.Size Ltr
100
Define the pulse size according to the water counter
specification.
Pulse Dly-Sec.
300
The "time out" definition during which the controller waits for
a water pulse before activating "no water pulse" alarm.
Fault React
Fault
The following options only apply when the irrigation unit is
by Time. If the irrigation unit is according to Volume it will
always create a fault.
Fault - Reaching the "time out" from the previous item issues
a fault message, stops the current valve and starts the next
valve in the sequence.
Two consecutive faults of this type causes the water meter to
fault and all of the valves using this water meter will not work.
Ignore - The controller continues irrigating.
Alarm - During this fault the controller issues an alarm but
does not stop irrigation.
Leak.Set-m3
5
The amount of water in M3 that the system allows when all
of the valves are closed before issuing the "leak" alarm. It
resets at the start of each irrigation.
Leak.Reaction
Fault
Fault - The controller will not allow irrigation and issues an
alarm.
Ignore - The programs using the water meter will irrigate
normally.
Alarm - During this fault the controller issues an alarm but
allows irrigation.
If the system has more than one water meter, access the next screen via the "Next" key.
Services
System Setup
Sequence Setup
Filter Flush
Fertilization
Sequence Timing
Valve • Water & Fert.
Water Counter
Diaries
Alarms
Valve Info
Sequence Info
Manual Overriding
Sequence Status
Valve Status
System Status
Summary of Contents for Gal Pro 4
Page 1: ...GalPro AC DC Operating Manual...
Page 2: ......