Location of the indoor unit
INSTALL LOCATION INSTRUCTION
Mount on the roof or truss solid enough to bear the weight of the indoor unit.
A place easy for air circulation around all corners.
Keep the air inlet and outlet at a far distance from the blockage.
Avoid places where there are steam, lampblack and inflammable gas.
Keep away from some equipment of high frequency. (Such as soldering machine)
Avoid places near the fire alarm, for hot air may trigger the fire alarm during heating.
Avoid places where there are spraying acidity liquor or sulphur.
Certain maintenance space must be left, please see the following requirement:
1. Ceiling
2. Ceiling inlaid board.
4. Maintenance space of 1m above.
5. Maintenance space of 50cm above.
3. Obstacle.
6. Panel
Location of the outdoor unit
Avoid direct sunshine.
Avoid strong wind.
Avoid places close to inflammable gas.
A place easy for conjunction with the power supply as well as with the indoor pipe.
A place where the operation noise will not annoy your neighbours.
Avoid installing on the shelf which may strengthen the noise and shake.
Watch for the condensation water discharging out of the chassis.
Arrange the height difference of both indoor and outdoor units, the length of
refrigerant pipe, number of bent position of pipe as the following requirement:
The indoor unit
A
B
C
30m
Lower than
15m
Less than
15
The outdoor
unit
Length of Pipe A (one way)
B:Height
difference
C: The number of
bent position of pipe
CHOICE OF INSTALL LOCATION
1
1
5
5
4
4
3
3
6
6
2
2
17
The appliance must not be installed in the laundry.
The appliance must be installed 2.3m above floor.