64
CODEDISTANCECLOSINGTIMESETUP(ACTUALVALUE)
To measure the Code Distance Closing Time, flip the 1
st
switch to SETUP. Press the
key . Physically move the door to the fully closed position. Record the count as
Count1. Move the door in the Open direction, away from DCL, 1 inch for Center Parting
doors, 2 inches for a Side Opening door. Record the count as Count2. Subtract Count1
from Count2. Enter the difference, Count2 minus Count1, of the Count into Par. 69. Do
the same procedure and enter the difference of the count into Par. 70 for the Narrower
door, if used. The display of the Code Distance Closing Time is in the sub-item #10
under the key as described in the Parameter Unit section of this manual.
VOLT
PULSE
VIEW
CENTERPARTING
CODE
DISTANCE
1”
1”
DCL
DOL
1”
RECORD
AS
COUNT1
RECORD
AS
COUNT2
FOR NORMAL/HEAVY DOOR
(COUNT2 –COUNT1)
Î
PAR. 69
FOR NARROW DOOR
(COUNT2 –COUNT1)
Î
PAR. 70
SIDEOPENING
CODE
DISTANCE
2”
2”
DCL
DOL
RECORD
AS
COUNT1
RECORD
AS
COUNT2
FOR NORMAL/HEAVY DOOR
(COUNT2 –COUNT1)
Î
PAR. 69
FOR NARROW DOOR
(COUNT2 –COUNT1)
Î
PAR. 70
64
Summary of Contents for MOVFE 2500
Page 1: ...2500 3069 1 888 425 2262 2500 3069 ELECTRICAL...
Page 2: ...Rev 1 10 20 I...
Page 24: ...19 6 DEFAULT PARAMETERS 19...
Page 26: ...21 FAULTS AN EXAMPLE OF FAULTS DISPLAY COUNTERS 21...
Page 27: ...22 USER LIST 22...
Page 28: ...23 23...
Page 29: ...24 24...
Page 30: ...25 25...
Page 31: ...26 MAXIMUM CLOSE SPEED AND FORCE 26...
Page 32: ...27 ECI DEFAULT PARAMETER SETS 27...
Page 34: ...29 SPEED PROFILES OF THE VFE2500 FOR NORMAL DOOR 29...
Page 35: ...30 SPEED PROFILES OF THE MOVFE2500 FOR HEAVY DOOR 30...
Page 36: ...31 SPEED PROFILES OF THE MOVFE2500 FOR NARROW DOOR 31...
Page 91: ...Rev 10 20 85...
Page 92: ......