56
Power and data transmission unit
Mounting und operating instructions
SECUREconnect 200
12.2013 | 15887EE | Printed in Germany
EN
7.3.2 Permanent OPEN (unlocking)
If a potential-free contact connected to terminals 91 / V4 is actuated with
the door closed, SECUREc
onnect
200F
receives the signal to retract the
latch.
The latch remains retracted permanently.
7.3.3 Door locking
If a potential-free contact (gating pulse) connected to terminals 92 / V4 is
actuated with the door closed, SECURE
connect
200F
receives the signal to
re-lock the electrical lock.
Here it may happen that the extended latchbolt
hits the striker.
In that case, please check the locking status of the
door.
ATTENTION
If the functions „Permanent OPEN“ and „Door
locking“ are controlled via a time switch and if the
input „Door locking“ is permanently closed, the
door can always be opened via the „Short-time
OPEN“ function.
NOTE
The electrical lock will not re-lock automatically.
The application of this function is not permitted
with fire rated doors (DIN 18250) ! Non-compliance
will result in the revocation of the door‘s
fire approval !
ATTENTION