![FW Murphy Centurion C5 M-VIEW MV-5-C Operationsmanual Download Page 8](http://html.mh-extra.com/html/fw-murphy/centurion-c5-m-view-mv-5-c/centurion-c5-m-view-mv-5-c_operationsmanual_2352719008.webp)
Section 50
00-02-1031
2019-08-07
- 2 -
MV-5-C Display
– Back Side
The LEDs are located next to the serial port connections.
All Ports RX/TX LEDs include:
The serial activity LEDs blink with every transmitted or received message.
o
The RX LED blinks Red when a packet is received by the display.
o
The TX LED blinks Green when a packet is transmitted by the display.
C5-1 Controller
NOTE:
The Expansion modules have the same 2 Power LEDs and COP blink codes as
the C5-1. They are located next to the power plug on all modules.
C5-1 Power LED Indicators
– Power is always two green LEDs
2 Green LEDs
:
2 on - Unit is powered normally
1 on - Internal power failure. Needs service
Off - No DC power to unit
C5-1 COP LED Indicators
– Controller Operating Properly
Green LED:
1 Blink/sec - Unit is running application normally
Fast blink - Bootloader mode
3 Blinks - Missing configuration
4 Blinks - Running in recovery mode
Off - Controller not operating