Section 50
00-02-1031
2019-08-07
- 38 -
Centurion Serial Ports Screen (Super User Password Protected)
Setup menu for the Centurion serial ports.
a)
485
– 1 / 2, FS BIAS:
Choose YES to enable
RS485 line fail-safe biasing. This should only be
done in one location on the RS485 network.
b)
485
– 1 / 2, Term RES:
Choose YES to enable a
120 ohm termination resistor on the bus. This
should be done at each end of the RS485
networks.
c)
485
–
1 / 2
,
Modbus Address:
Display/Set the
Modbus RTU slave address for the serial port.
d)
485
–
1 / 2,
Reply Delay (0 - 65535mS):
Optional
time delay for the Modbus response.
e)
485
–
1 / 2,
Baud Rate:
Select the appropriate
transmission baud rate from these six choices
(9600, 19200, 38400, 57600, 115200)
f)
232
– 1 / 2, Modbus Address:
Display/Set the
Modbus RTU slave address for the serial port.
g)
232
– 1 / 2, Reply Delay (0 - 65535mS):
Optional
time delay for the Modbus response.
h)
232
– 1 / 2, Baud Rate:
Select the appropriate
transmission baud rate from these six choices
(9600, 19200, 38400, 57600, 115200)
NOTE:
The port 2 is set by the DIP switch and is read only
from the display.
NOTE:
All ports use no parity, 8 data bits, 1 stop bit:
Centurion CAN Ports Screen (Super User Password Protected)
Setup menu for the Centurion CANBUS ports
CAN0 / 1 Address:
Set the CAN address for the
Centurion
CAN0 / 1 Arbitrary:
Set to YES to allow the port to be
Arbitrary address capable
CAN0 / 1 Term RES:
Displays the status of the 120 ohm
termination resistor on the bus. This is set by DIP switch 9
and 10. This should be done at each end of the CAN
networks.
Lost CAN0 DLY:
Time delay for configuring the loss of
comm detection for devices on the CAN port.