Operation
SYMBOL
DESCRIPTION
DEFAULT VALUE
FULTON VALUE
CUSTOMER VALUE
IN
Input Type
1
4
UNIT
Input Unit Selection
C
F
RH
Range High
variable
210
RL
Range Low
variable
0
SDP
Scale Decimal Point
1
1
SH
Scale High
100
0
SL
Scale Low
0
0
RJC
On/Off
on
on
BSL
Burnout Selection
1
1
OT
Output type
0
2
RET
Retransmission
1
1
RTH
Retransmission High
variable
210
RTL
Retransmission Low
variable
0
DIS
Digital Input
off
off
C.S1
Custom Select
off
off
C.S2
Custom Select
off
off
C.S3
Custom Select
off
off
C.S4
Custom Select
off
off
LOCK
Key Lock
off
off
PWD
Password
0
0
Worksheets for Yokogawa UT320/UT350
Temperature Control Program for
Pulse Modulating Water Heaters
Input/Output Menu
Functional Parameters
SYMBOL
DESCRIPTION
DEFAULT VALUE
FULTON VALUE
CUSTOMER VALUE
AL1
Alarm 1 Type
1
4
AL2
Alarm 2 Type
2
off
AL3
Alarm 3 Type
3
off
HY1
Alarm 1 Hysteresis
0.5
10
HY2
Alarm 2 Hysteresis
0.5
off
HY3
Alarm 3 Hysteresis
0.5
off
CT
Control Output Type
30
1
CTc
Control Output Type
30
same
PO
Preset Output
0
0
Poc
Preset Output Cooling
0
0
C.MD
PID Control
0
0
ZON
Zone PID Control
off
off
AR
Anti-Reset Windup
auto
auto
TMU
Time Unit for Ramp
0
1
P.SL
Protocol Selection
0
0
BPS
Communication Speed
4
4
PRI
Parity
1
1
STP
Stop Bit
1
1
DLN
Data Length
8
8
ADR
Address
1
1
RP.T
Minimum Response Time
0
0
TEST
Test Control
0
0
Note: Parameters with bold values only will be used.
Note: Parameters with bold values only will be used.
31-PDWH
Summary of Contents for PDWH1000
Page 5: ...Section 1 Safety Warnings and Precautions 3 PDWH...
Page 9: ...Section Installation 7 PDWH 2...
Page 28: ...PAGE INTENTIONALLY LEFT BLANK...
Page 29: ...3 Operation Section 26 PDWH...
Page 37: ...Section 4 Maintenance 34 PDWH...
Page 41: ...Section 5 Parts and Warranty 38 PDWH...
Page 42: ...PAGE INTENTIONALLY LEFT BLANK...
Page 46: ...PAGE INTENTIONALLY LEFT BLANK 42 PDWH...
Page 48: ...PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...PAGE INTENTIONALLY LEFT BLANK...