Introduction
The Fulton Pulse water heater is an
automatic gas fired, direct vent water
heater. This water heater utilizes the pulse
combustion principle. It requires no
conventional burner controls, no pilot and
no flue or chimney. The combustion
components are of integral design with the
heat exchanger. For combustion, the water
heater uses 100% outside air supplied
through schedule 40 PVC pipe.
The products of combustion are vented
outdoors through non-corrosive venting
materials which will withstand 480°F
(249°C) temperatures. These pipes can be
routed either through a roof or through the
side wall of a building. Each water heater
is built to ASME and CSD-1 Codes,
hydrostatically tested, test fired, and
shipped as a complete packaged unit.
Gas, water, and electrical connections are
similar to conventional water heaters.
All installations must be in accordance with
the American National Standard “National
Fuel Gas Code,” latest edition, and with
the requirements of local utilities or other
authorities having jurisdiction. Such
applicable requirements take precedence
over the general instructions herein.
Since an external electrical source is
utilized, the water heater, when installed,
must be electrically grounded in
accordance with the National eectrical
Code, ANSI/NFPA 70-latest edition.
In some cases the approval authority may
insist that the installation conform to the
American Society of Mechanical Engineers
ASME safety standard for controls and
safety devices for automatically fired water
heaters, or CSD-1.
In Canada, gas installations must be in
accordance with the current CAN/CGA
B149.1 and .2 and/or local codes.
Electrical installations must be installed in
accordance with the current CSA C22.1
Canadian Electrical Code and/or local
codes.
The following items
are standard trim
for Fulton Pulse
water heaters:
Full Modulation with a 5:1 turndown ratio
Fully Insulated
Microprocessor Based Control - 120 volt
Low Water Cutoff (Probe Type)
Control Panel Completely Wired with
Diagram
Operating Temperature Control
Hi-Limit Temperature Control w/ Manual
Reset
Air Pressure Switch
Spark Ignition
Main Motorized Gas Valve
Main Gas Pressure Regulator
Manual Lubricated Gas Cock
Second Gas Valve (Solenoid)
Included with and
packaged separately
with each water heater
are the following
components:
ASME Pressure Relief Valve
Pressure-Temperature Gauge
Air Intake and Exhaust Pipe Adaptors
Installation, Operation, and Maintenance
Manual
Elastomer Coated Fiberglass Cubes
Gas and Water Flex Connectors
Intake and Exhaust Mufflers
Optional Accessories
Condensate Liquid Drainer
Flex Connectors
Spring Mounts
Installation
General specifications and information about Fulton
Pulse Potable Water Heaters:
Models
PDWH750
PDWH1000
BTU/HR. Input
750,000
1,000,000
BTU/HR Output*
660,000
880,000
Fuel
NG/LPG
NG/LPG
Approx. Dry Weight
1,800 lbs.
1,400 lbs.
Approx. Operating Weight
2,150 lbs.
2,150 lbs.
Floor Loading
300 lbs/ft2
300 lbs/ft2
Power Required
120/60/1
120/60/1
Min. Required
7" W.C.NG
7" W.C. NG
Gas Pressure
11" W.C. LPG
11" W.C. LPG
Max. Amp Draw (F L.A.)
4.0
4.0
MAWP
160 PSI
160 PSI
Water heater Width
27.5 IN
27.5 IN
Water heater Height
76 IN
76 IN
Water heater Depth
37.8 IN
37.8 IN
GPH @100°F
Temperature Rise
790
1055
Note: *Based on 40°F in -140°F out.
8-PDWH
Summary of Contents for PDWH1000
Page 5: ...Section 1 Safety Warnings and Precautions 3 PDWH...
Page 9: ...Section Installation 7 PDWH 2...
Page 28: ...PAGE INTENTIONALLY LEFT BLANK...
Page 29: ...3 Operation Section 26 PDWH...
Page 37: ...Section 4 Maintenance 34 PDWH...
Page 41: ...Section 5 Parts and Warranty 38 PDWH...
Page 42: ...PAGE INTENTIONALLY LEFT BLANK...
Page 46: ...PAGE INTENTIONALLY LEFT BLANK 42 PDWH...
Page 48: ...PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...PAGE INTENTIONALLY LEFT BLANK...