Pipe Capacity For Natural Gas
Nominal
Equivalent
Iron Pipe
Internal
Pipe Length
Size
Diameter
90Þ Elbow
Tee
Inches
Inches
Feet
Feet
20
40
60
80
100
150
200
1.25
1.38
3.50
6.90
950
—
—
—
—
—
—
1.50
1.61
4.00
8.00
1460
990
810
—
—
—
—
2.00
2.07
5.20
10.30
2750
1900
1520
1300
1150
950
800
2.50
2.47
6.20
12.30
4350
3000
2400
2050
1850
1500
1280
3.00
3.07
7.70
15.30
7700
5300
4300
3700
3250
2650
22780
4.00
4.03
10.10
20.20
15800
10900
8800
7500
6700
5500
4600
Installing Gas Piping
Figure 4
NOTE
See the above chart for required pipe
size, based on overall Iength of pipe
from meter plus equivalent length of all
fittings. Approximate sizing may be
based on 1,000 BTU for 1 cubic foot of
natural gas.
1. Gas Piping should be installed in
accordance with National Fuel Gas
Code, ANSI Z223 1 1991 or latest
addenda and any other local codes
which may apply.
In Canada gas installations must be in
accordance with the current CAN/CGA
B149.1 and .2 and/or local codes.
2. The pipe and the fittings used should
be new and free of dirt or other deposits
Piping must be of the proper size to
ensure adequate gas supply.
3. Gas pressure to inlet of gas train
should be 7" WC. for natural gas and
11" WC. for propane. Connect gas
supply line to the open end of the tee
on which the drip leg is installed.
4. When making gas piping joints, use
a sealing compound resistant to the
action of liquefied petroleum gases. Do
not use teflon tape on gas line threads.
5. After gas piping is completed and
before wiring installation is started,
carefully check all piping connections,
(factory and field), for gas leaks. Use a
soap and water solution.
CAUTION
Some soaps used for leak testing are
corrosive to certain types of metals. Rinse
all piping thoroughly with clean water
after leak check has been completed.
6. The water heater must be
disconnected at the water heater shut
off valve from the gas supply piping
system during any pressure testing of
the system at pressure in excess of
1
/
2
psig (14" WC)(3.5 kPa).
7.The water heater must be isolated
from the gas supply piping system by
closing its individual manual shut off
valve during any pressure testing of the
gas supply system at test pressures
equal or less than 1/2psi (3.5kPa).
8. Gas vents to outdoor air must be
provided for the pressure regulator and
gas pressure switches. Restricting
orifices or bleed orifices should not be
used at anytime.
WARNING
Do not use matches, candles, flame or
other sources of ignition to check for
gas Ieaks.
NOTE
The vent line connection on the gas
pressure regulator and the low and high
gas pressure switches must be piped
to outdoor air by installer in accordance
with the National Fuel Gas Code, ANSI
Z223- 1-1991 or latest addenda.
In Canada gas installations must be in
accordance with the current CAN/CGA
B149.1 and .2 and/or local codes.
Installation
Figure 4
Maximum Capacity in Cubic Feet of Natural Gas Per Hour
Pressure Drop of 0.5" W.C.
Equivalent Length of Pipe in Feet
13-PDWH
CANADA
US
Summary of Contents for PDWH1000
Page 5: ...Section 1 Safety Warnings and Precautions 3 PDWH...
Page 9: ...Section Installation 7 PDWH 2...
Page 28: ...PAGE INTENTIONALLY LEFT BLANK...
Page 29: ...3 Operation Section 26 PDWH...
Page 37: ...Section 4 Maintenance 34 PDWH...
Page 41: ...Section 5 Parts and Warranty 38 PDWH...
Page 42: ...PAGE INTENTIONALLY LEFT BLANK...
Page 46: ...PAGE INTENTIONALLY LEFT BLANK 42 PDWH...
Page 48: ...PAGE INTENTIONALLY LEFT BLANK...
Page 49: ...PAGE INTENTIONALLY LEFT BLANK...