17.ALARMS
17.4.4 Individual pressure switch alarms:
The
RCK-862
plus
can control up to 3 individual pressure switches. The address of each pressure
switch in the alarm nomenclature is represented by the letter ‘’x’’. Where ‘’x’’ can be 7, 8 or 9 and represents, respectively, the individual pressure
switches 1, 2 or 3.
Example:
Alarm
Alarm
Effect
Effect
Description
Description
AL0x01
ALxx01
AL0x02
ALxx02
Low pressure
Low temperature
High pressure
High temperature
Indicative alarm
Shut off the output
Shut off the output
Indicative alarm
Shuts off all outputs ignores the time between
shutdowns
AL0x03
Pressure sensor fault
AL0x01
AL0x01
AL0x01
7 - Referring to individual pressure switch 1
8 - Referring to individual pressure switch 2
9 - Referring to individual pressure switch 3
7 - Referring set of outputs 1
8 - Referring set of outputs 2
9 - Referring set of outputs 3
10 - Referring to individual thermostat switch 1
11 - Referring to individual thermostat switch 2
12 - Referring to individual thermostat switch 3
13 - Referring to individual thermostat switch 4
14 - Referring to individual thermostat switch 5
15 - Referring to individual thermostat switch 6
17.4.5 Individual thermostat alarms:
The
RCK-862
plus
can control up to 6 individual thermostats. The address of each thermostat
in the alarm nomenclature is represented by the letter ‘’x’’. Where ‘’x’’ can be 10, 11, 12, 13, 14 and 15, representing the individual
thermostats 1, 2, 3, 4, 5 or 6, respectively.
Example:
Shut off the output
Temperature sensor fault
ALxx03
Alarm
Effect
Alarm
Effect
Description
Description
ALxx01
AL1901
ALxx02
AL1902
AL1906
AL1904
AL1908
AL1910
Output 1 alarm
No communication with expansion 1
No communication with expansion 2
No communication with expansion 3
No communication with expansion 4
No communication with expansion 5
No communication with expansion 6
No communication with expansion 7
No communication with expansion 8
No communication with expansion 9
No communication with expansion 10
Output 2 alarm
Shut off output 1 and actuate output 2
Shut off all controller outputs
(except alarm outputs)
Shut off all controller outputs
(except alarm outputs)
Shut off all controller outputs
(except alarm outputs)
Shut off all controller outputs
(except alarm outputs)
Shut off all controller outputs
(except alarm outputs)
Shut off all controller outputs
(except alarm outputs)
Shut off all controller outputs
(except alarm outputs)
Shut off all controller outputs
(except alarm outputs)
Shut off all controller outputs
(except alarm outputs)
Shut off all controller outputs
(except alarm outputs)
Shut off output 2 and actuate output 1
17.4.6 Rotating output alarms :
The
RCK-862
plus
can control up to 3 sets of rotating outptus. The address of each set of rotating
outputs in the alarm nomenclature is represented by the letter ‘’x’’. Where ‘’x’’ can be 16, 17 and 18, representing sets of outputs 1, 2 or 3,
respectively.
Example:
17.4.7 Communication alarms with expansions:
AL1903
AL1907
AL1905
AL1909
42