13.CONTROL MENU
The Control Menu is accessible by pressing the
key, has settings and commands for easy access to the operations of the
RCK-862
plus
.
ddd
7
10
11
8
9
12
13
14
15
1
6
2
3
4
5
Access control
:
According to the access level, the user can take different action on the
RCK-862
plus
. You can adjust 3 access levels:
- Viewer:
Standard mode, there is no need to enter code.
- Technical:
Allows you to make changes to some system parameters.
Technical level is activated by entering code 123.
- Administrator:
Allows you to make changes to all system parameters (normally
used when performing the initial system configuration).
Administrator level is activated by entering code 717.
In an invalid code is entered or the
RCK-862
plus
is idle for 15
minutes, it automatically returns to Viewer mode.
Adi
abatic Condensation:
Enables and disables adiabatic condensation logic for each
discharge pressure switch.
Floating Condensation
:
Enables and disables floating condensation logic for
each disacher pressure switch.
Hou
r meters:
Indicates the number of hours that each compressor or
fan remained in operation.
C o m p r e s s o r p r o t e c t i o n
thermostat:
View of compressor protection thermostats.
Inputs and outputs
:
A summary of the
RCK-862
plus
inputs and outputs
is displayed, indicating the sensor reading value, the
status of the digital inputs and control outputs.
M
ainten
ance:
Compressors or fans are viewed and selected to enter
maintenance mode. When the equipment is in the
maintenance state, it remais off.
Dat
e
and
time
:
Adjusts the current date and time. This field is
important for alarm and logic records that use a clock.
Indi
vidual pressure switch:
View of the summary screens of the individual
pressure switches.
In
dividual thermostat:
View of the summary screens of the individual
thermostats.
Rotation outputs
:
View of the screens of the sets of outputs with rotation.
Control status
:
You can turn the system control on or off. When turned off, the
RCK-
862
plus
only monitors the system but without taking any action.
Note:
Changing some functions such as downloading recipes
requires that the controller be turned off.
Resetting alarms:
Reset the pressure switches in manual or automatic reset condition.
Once the resetting is done, this will be recorded in the alarm history.
Econom
y setpoint:
Activates the economic setpoint for each group of pressure switches.
Pump Down:
Activates the Pump Down function for each group of pressure switches.
Contro
l menu:
Control status
Resetting alarms
Economic setpoint
Inputs and outputs
Dat
e
and time
Individual Thermostat
Pump Down
Adiabatic Cond.
Floating Cond.
Therm. Compressors
Ma
intenance
Individual Pressure Switch
Rotating outputs
Hour meters
Access control
9
13
15
7
11
5
3
1
10
8
12
14
6
4
2
19